4049
RW
-1440...0...1440
[
o
/
oo
]
Continuous output 1 - lower value of
the input range in [
o
/
oo
] of the rated
input range
0
4050
RW
-1440...0...1440
[
o
/
oo
]
Continuous output 1 - upper value of
the input range in [
o
/
oo
] of the rated
input range
1000
4051
RW
-2400...0...2400
[10 A]
Continuous output 1 - lower value of
the current output range [
10 A]
0
4052
RW
1...2400 [10 A]
Continuous output 1 - upper value of
the current output range [
10 A]
2000
4053
RW
0...2
Continuous output 1 - manual switch-
ing on: 0 - normal work,
1- value set from the register 4051,
2 - value made from the register 4052
0
4054
RW
-24...24 [mA]
Continuous output 1 - value on the
output by error
24
4055
RW
0,1...35
Continuous output 2 - quantity on the
output (code acc. to the tab.6)
24
4056
RW
0...2
Continuous output 2 -
type:
0 - (0 ...20) mA; 1 - (4...20) mA;
2 - (-20...20) mA
2
4057
RW
-1440...0...1440
[
o
/
oo
]
Continuous output 2 - lower value of
the input range in [
o
/
oo
] of the rated
input range
0
4058
RW
-1440...0...1440
[
o
/
oo
]
Continuous output 2 - upper value of
the input range in [
o
/
oo
] of the rated
input range
1000
4059
RW
-2400...0...2400
[10 A]
Continuous output 2 - lower value of
the current output range [
10 A]
0
4060
RW
1...2400 [10 A]
Continuous output 2 - upper value of
the current output range [
10 A]
2000
4061
RW
0...2
Continuous output 1 - manual switch-
ing on: 0 - normal work,
1- value set from the register 4059,
2 -value made from the register 4060
0
4062
RW
-24...24 [mA]
Continuous output 2 - value on the
output by error
24
4063
RW
0,1...35
Continuous output 3 - quantity on the
output (code acc. to the tab.6)
24
38
38
Summary of Contents for CON-M 22
Page 1: ...ZIEGLER CON M PROGRAMMABLE MULTI TRANSDUCER OPERATING MANUAL 15001298_Rev _B_04 2014 ...
Page 2: ......
Page 8: ...Direct measurement in a four wire network Multi transducer 8 8 ...
Page 9: ...Measurement with the use of current transformers in a four wire network Multi transducer 9 9 ...
Page 17: ...Fig 9 Con guration of the connection with the Multi transducer Multi transducer 17 17 ...
Page 57: ...57 57 NOTE ...
Page 58: ...58 58 NOTE ...
Page 59: ...59 59 ...
Page 60: ...60 60 NOTE ...