Regi-
ster
ad-
dress
Ope-
ra-
tions
Range
Description
By
De-
fault
4000
RW
0
Reserved
0
4001
RW
0
Reserved
0
4002
RW
0
Reserved
0
4003
RW
1...10000
Current transformer ratio
1
4004
RW
1...40000
Voltage transformer ratio x 10
10
4005
RW
0...3
Synchronization of mean active
power:
0 –15 minutes’ walking window
(recording synchronized
every 15 min with the clock.)
1 – measurement synchronized
every 15 min with the clock.
2 – measurement synchronized
every 30 min with the clock.
3 – measurement synchronized
every 60 min with the clock.
0
4006
RW
0
Reserved
0
4007
RW
0.1
The way of minimal and maximal
value recording
0 -without errors, 1 - with errors
0
4008
RW
0.1
Reserved
0
4009
RW
0...2359
The way of reactive energy
calculation
0 -without errors, 1 - with errors
0
4010
RW
0...1440
Ordered power
1000
4011
RW
0..3
Erasing of energy counter:
0 - without changes, 1 - erase
active energy, 2 - erase passive
energy, 3 - erase all energy
0
4012
RW
0.1
Erasing of mean active power P
AV
0
4013
RW
0.1
Erasing of mean active power
P
AV
archive
0
4014
RW
0.1
Erasing of min. and max.
0
Table 5
35
35
Summary of Contents for CON-M 22
Page 1: ...ZIEGLER CON M PROGRAMMABLE MULTI TRANSDUCER OPERATING MANUAL 15001298_Rev _B_04 2014 ...
Page 2: ......
Page 8: ...Direct measurement in a four wire network Multi transducer 8 8 ...
Page 9: ...Measurement with the use of current transformers in a four wire network Multi transducer 9 9 ...
Page 17: ...Fig 9 Con guration of the connection with the Multi transducer Multi transducer 17 17 ...
Page 57: ...57 57 NOTE ...
Page 58: ...58 58 NOTE ...
Page 59: ...59 59 ...
Page 60: ...60 60 NOTE ...