OPERATION
Page 4
2.0 OPERATION
2.1 DC P
OWER
O
N
When control system DC power is turned ON:
• Processor will command Neutral/Idle.
• Intermittent tone will sound at all Stations indicating that no Station
has command.
(refer to Section 2.6
2.2 E
NGINE
S
TART
I
NTERLOCK
Features related to main engine start:
Start Interlock
to block the engine start signal if the DC power has
not been turned ON.
Start Interlock
to block the engine start signal if no Station has
command.
Start Interlock
to block the engine start signal if clutch is engaged.
Start Interlock
will block the engine start signal if the Set-up Mode
Jumper is Closed on the Main Circuit Board. Refer to
Figure 14:, page 26, for location of the Jumper.
The Processor is interlocked to prevent engine Start until power is ON
and the transmission is in Neutral. The engine Start signal will be con-
nected through the Processor to the starter solenoid or relay.
To take command at a Station:
• Control Head lever(s) must be in the Neutral
(vertical) detent.
• Operator must depress the transfer button for
at least 1/2 second.
The tone will stop at all Stations and the red indi-
cator light will be lit at the Station-in-Command.
Figure 1: Control Head Detents
NOTE: Only one Station has command at a time.
Summary of Contents for ClearCommand
Page 56: ......
Page 57: ...APPENDIX A 1 ...
Page 58: ......
Page 60: ...Appendix A 6 20 01 Page 2 ...
Page 63: ...Page 5 ...
Page 64: ...Page 6 ...
Page 68: ...Page 10 ...
Page 70: ...Page 12 ...
Page 72: ...Page 14 ...
Page 78: ...Page 20 ...
Page 82: ...Page 24 ...
Page 85: ...APPENDIX B 1 ...
Page 86: ......
Page 97: ...APPENDIX C 1 ...
Page 98: ......
Page 99: ...Drawing 11202F 1 ...
Page 100: ... ...
Page 101: ...Drawing 11202F 2 ...
Page 102: ... ...
Page 103: ...Drawing 11202F 3 Notes Page ...
Page 104: ... ...