Web Server
~
29
~
Parameter
Definition
E
Q value: The reactive value of inverter when
received the AS DRM7 Command
f
It expect power reading of the energy meter
b)
Active power feed-in at over frequency Limit
The Load speed is setted for inverter load speed when reconnection.
The Fig. 6-10: Set active power feed-in at over frequency Limit
c)
Active power feed-in at over volt Limit
The Fig. 6-11: Set active power feed-in at over volt limit
d)
Reactive Power Limit
There are four modes of reactive power limitation which can be selected.
Cos(phi) fix mode: In this mode, the ZeverCom/ZeverCom WiFi will regulate
the reactive power of inverter according to the Cos(phi) value which is set
by the user. Enter the Cos(phi) value and choose the phase as shown in Fig.
6-12.
Fig. 6-12: Cos(phi) fix mode