background image

INFINITY 8 INSTALLATION MANUAL 

Approved Document No. GLT-201-7-1 

 

PAGE 2 

Issue: 1.6      Author:  NRPJ          Date: 27/7/2012 

1. INTRODUCTION 

THIS FIRE ALARM CONTROL PANEL IS CLASS 1 EQUIPMENT AND MUST BE EARTHED. 

This equipment must be installed and maintained by a qualified and technically experienced person. 

1.1 HANDLING THE PCBS 

If the PCBs are to be removed to ease fitting the enclosure and cables, care must be taken to avoid damage by static. 

The best method is to wear an earth strap, but touching any earth point (e.g. building plumbing) will help to discharge any static. 
Hold PCBs by their sides, avoiding contact with any components. 

Always handle PCBs by their sides and avoid touching the legs of any components. Keep the PCBs away from damp dirty areas, e.g. 
in a small cardboard box. 

1.2 USING THIS MANUAL 

This manual explains, in a step-by-step manner, the procedure for the installation of the Infinity 8 Range of Fire Alarm Control 
Panels.  For full operational and maintenance information, please refer to document GLT.MAN- (USER MANUAL, MAINTENANCE 
GUIDE & LOG BOOK).  It also contains a System set-up table, and Installation Certificate, that must be completed by the 
Commissioning Engineer prior to system handover. 

Unlike the User Manual, this Installation Manual must not be left accessible to the User. 

1.3 ABOUT THE INFINITY FIRE ALARM CONTROL PANEL & INTEGRAL PSE 

 

The Infinity Fire alarm control panel is available in 
1,2,4,6 or 8 Zone sizes. 

 

The 1 & 2 zone panels have 2 x 250mA sounder 
circuits. 

 

The 4, 6 & 8 zone panels have 4 x 150mA sounder 
circuits. 

 

It has a set of fire relay contacts (voltage free) rated at 
1A SELV. 

 

It has a set of fault relay contacts (voltage free) rated 
at 1A SELV. This relay is normally powered to allow a 
fault output in the case of total power failure. 

 

It has the ability to disable any zone or the sounder 
circuits. 

 

It has a one man test mode, which resets the Zone in 
test after 5 seconds (EN54 option with requirements). 

 

It has a sounder delay facility (0-10 minutes in 1 
minute steps)(EN54 option with requirements). 

 

It has a maximum battery capacity of 3.4Ah. 

 

It has an in built capability of operating with Diode 
bases (for line continuity on head removal). 

 

It will operate in ambient temperatures of -5 to 40°C. 

 

It will operate in a relative humidity of up to 93% 
(non-condensing). 

 

It will withstand vibrations between 5 & 150 Hz. 

 

It has a maximum capacity of 32 devices per zone. 

 

The PSE is a 35W Switch Mode cage with a nominal 
output of 30V. 

 

The battery is fused at 2A (quick blow). 

 

The PSE will draw a maximum of 30uA from the 
battery in the event of mains failure (the FACP will 
continue to take around 60mA). 

 

The FACP & PSE should be maintained as described in 
section 3 of the User Manual, Maintenance Guide & 
Log Book. 

1.4 DESIGNING THE SYSTEM 

This manual is not designed to teach Fire Alarm System design. It is assumed that the installer has an understanding of Fire Alarm 
System components and their use. 

We strongly recommend consultation with a suitably qualified, competent person regarding the design of the Fire Alarm System. 
The System must be commissioned and serviced in accordance with our instructions and the relevant National Standards.  Contact 
the Fire Officer concerned with the property at an early stage in case he has any special requirements. 

If in doubt, read BS 5839: Pt 1: 2002 “Fire Detection and Fire Alarm Systems for buildings (Code of Practice for System Design, 
Installation, Commissioning and Maintenance)” available from the BSI, or at your local reference library. 

 

1.5 EQUIPMENT GUARANTEE 

If this equipment is not fitted and commissioned according to our guidelines, and the relevant National Standards, by an approved 
and competent person or organisation, the warranty may become void. 

Summary of Contents for INFINITY 8

Page 1: ...INFINITY 8 INSTALLATION MANUAL Approved Document No GLT 201 7 1 Issue 1 6 Author NRPJ Date 27 7 2012 FIRE ALARM CONTROL PANEL INSTALLATION MANUAL...

Page 2: ...S 5 FIELD DEVICE TERMINATION 5 1 TERMINATING THE DETECTION AND ALARM SOUNDER CIRCUITS 5 2 AUXILIARY OUTPUT TERMINATIONS 6 SOUNDER ACTIVATION DELAY 6 1 DECIDING TO USE A DELAY 6 2 TO SET A DELAY 6 3 WI...

Page 3: ...wer failure It has the ability to disable any zone or the sounder circuits It has a one man test mode which resets the Zone in test after 5 seconds EN54 option with requirements It has a sounder delay...

Page 4: ...taller Engineer Open enclosure Connect wiring during install Battery check during Maintenance Set configuration switches 4 Authorised Service Engineer Open enclosure PC programming software Update pan...

Page 5: ...d mechanical protection such as a conduit 2 2 MAINS WIRING RECOMMENDATIONS The Mains supply to the FACP is fixed wiring using Fire resisting 3 core cable Between 1 mm and 2 5mm or a suitable 3 conduct...

Page 6: ...of old mechanical bell or a relay are used then a diode will have to be placed in line with the device to enable fault monitoring They may also need a back EMF protection diode 2 5 AUXILIARY OUTPUT W...

Page 7: ...AL Approved Document No GLT 201 7 1 PAGE 6 Issue 1 6 Author NRPJ Date 27 7 2012 The termination for the above inputs must be as indicated on the main PCB See page 15 The Earthing of the cable screens...

Page 8: ...x If a grommet is removed fill the hole with a brass cable gland If any knockout is removed but subsequently not used it should be covered up The 230Va c Mains cable must be fed into the enclosure via...

Page 9: ...WER 4 1 CONNECTING THE MAINS POWER Figure 3 Power Supply PCB layout and Mains connection details Figure 3 4 2 CONNECTING THE BATTERIES Figure 4 Battery location and connection details CAUTION RISK OF...

Page 10: ...l screens should be fed through the gland to make electrical contact with it and be terminated at the brass earthing strip as shown below see Figure 6 For detailed detector and alarm circuit wiring di...

Page 11: ...he number with the keypad 0 minutes type nothing 9 minutes type 81 10 minutes type 82 Press 5 The panel will flash a confirmation of the selected delay 6 Press 3 times to exit access level 3 6 3 WIRIN...

Page 12: ...isable one zone at a time 1 Enter access code default 1245 and press 2 Press for 3 seconds 3 Type the number of the zone you want to disable If you wish to disable the sounders press 4 Press to disabl...

Page 13: ...not in test mode at this point 4 Press to start test mode The Zone test LEDs will be flashing with a pattern 12 flashes then a pause repeated The zone is now in test mode 5 To set a different zone int...

Page 14: ...ase that is not making the connection c A short circuit on a zone could be caused by the end of line diode being fitted backwards d Check that the detectors are compatible with this FACP Note that som...

Page 15: ...nect the earth screens one at a time to determine the problem line Note connecting other equipment e g an oscilloscope to the panel can give an earth fault 9 5 SOUNDER FAULTS Similar to the zone fault...

Page 16: ...00005 Amp 50 A Optical Detector 0 0001 Amp 100 A Typical Example A system comprises of 20 ionisation detectors 14 bells and the required standby is 24 hours It will need to operate in alarm for hour...

Page 17: ...bells 10 SND 2 Connect to sounder circuit 2 sirens bells 11 SND 3 Connect to sounder circuit 3 sirens bells 12 SND 4 Connect to sounder circuit 4 sirens bells 13 FAULT RELAY NC CM NO Normally powered...

Page 18: ...TAGE 22 5V DC NOMINAL SOUNDER ALARM OUTPUTS 2 x 150mA 24V DC 1 2 zone panel 4 x 150mA 24V DC 4 6 8 zone panel AUXILIARY FAULT OUTPUT 1 x RELAY SELV 1A MAX AUXILIARY FIRE OUTPUT 1 x RELAY SELV 1A MAX N...

Page 19: ...e condition Giving 2 fire relays Switch 8 ON Makes the last zone on the panel a call point zone alarms from that zone not delayed Note The above options my not comply with local regulations Please che...

Reviews: