background image

INFINITY 8 INSTALLATION MANUAL 

Approved Document No. GLT-201-7-1 

 

PAGE 10 

Issue: 1.6      Author:  NRPJ          Date: 27/7/2012 

6. SOUNDER ACTIVATION DELAY 

6.1 DECIDING TO USE A DELAY 

A delay of up to ten minutes from the Fire Alarm Panel being triggered, to its Alarm sounder outputs being activated, can be 
programmed into the panel by the Engineer.  This is a particularly useful feature for schools, nightclubs and other public places 
where the nuisance and panic caused by a false alarm must be avoided. It should be noted that the delay period will apply to ALL 
DETECTOR zones. Call point Zones will not be delayed. 

When a sounder delay is used, zone 1 is designated as a call point zone, and an alarm in this zone will not be delayed. There is an 
option to define the last zone as a call point zone also (see section 13: Engineer Options). All other zones will be designated as 
detector zones. 

When an Alarm occurs on any detector zone, it is processed as normal.  However, the activation of the sounders is postponed until 
the delay period has expired, thus allowing the cause of the Alarm to be investigated by the User. If the alarm is false the alarm can 
be cancelled. 
 

6.2 TO SET A DELAY 

1.

 

Enter the access code (default 1245) and press  

2.

 

Enter access level 3 (

1246

) and press 

3.

 

Hold 

 for 3 seconds. 

4.

 

Type in the number of minutes you require the delay to be: 

 

1-8 minutes type the number with the keypad. 

 

0 minutes type nothing. 

 

9 minutes type 

81

 

10 minutes type 

82

Press 

5.

 

The panel will flash a confirmation of the selected delay. 

6.

 

Press 

 3 times to exit access level 3. 

6.3 WIRING CONSIDERATIONS WHEN USING A DELAY 

A delay is not usually applied to manual call points, unless there are exceptional circumstances to be taken into consideration.  

In order to meet this requirement, call points should be connected to a zone that is not delayed.  

On the infinity panel, zone 1 is never delayed, so call points should be connected to zone 1. If more than one 'call point zone' is 
needed, the last zone on the panel can also be set as non-delayed by setting configuration dip switch 8 to the on position. 

6.4 DELAY INDICATION AND OVERRIDE 

If a delay is set, the fire panel will light the Delay (SOUNDER DELAY) LED to indicate that the sounders are delayed. If an alarm 
occurs, the fire LEDs will light as usual, but the sounders will not start until the delay period has expired. After the delay period, the 
Delay LED will extinguish & the sounders will start. 

Pressing the 

 switch will override the delay at any time and results in the sounders being turned on immediately. 

If on investigation, the panel was activated by a false alarm, enter the access code to enable the Controls, and press the reset 
button. This will return the system to normal, without the sounders being activated. (Assuming the cause of the false alarm has 
been removed). 

The delay can be toggled on/off: 

1.

 

Enter access code (1245) press 

2.

 

Press  

3.

 

Press  

 again to deactivate sounder delay. 

Summary of Contents for INFINITY 8

Page 1: ...INFINITY 8 INSTALLATION MANUAL Approved Document No GLT 201 7 1 Issue 1 6 Author NRPJ Date 27 7 2012 FIRE ALARM CONTROL PANEL INSTALLATION MANUAL...

Page 2: ...S 5 FIELD DEVICE TERMINATION 5 1 TERMINATING THE DETECTION AND ALARM SOUNDER CIRCUITS 5 2 AUXILIARY OUTPUT TERMINATIONS 6 SOUNDER ACTIVATION DELAY 6 1 DECIDING TO USE A DELAY 6 2 TO SET A DELAY 6 3 WI...

Page 3: ...wer failure It has the ability to disable any zone or the sounder circuits It has a one man test mode which resets the Zone in test after 5 seconds EN54 option with requirements It has a sounder delay...

Page 4: ...taller Engineer Open enclosure Connect wiring during install Battery check during Maintenance Set configuration switches 4 Authorised Service Engineer Open enclosure PC programming software Update pan...

Page 5: ...d mechanical protection such as a conduit 2 2 MAINS WIRING RECOMMENDATIONS The Mains supply to the FACP is fixed wiring using Fire resisting 3 core cable Between 1 mm and 2 5mm or a suitable 3 conduct...

Page 6: ...of old mechanical bell or a relay are used then a diode will have to be placed in line with the device to enable fault monitoring They may also need a back EMF protection diode 2 5 AUXILIARY OUTPUT W...

Page 7: ...AL Approved Document No GLT 201 7 1 PAGE 6 Issue 1 6 Author NRPJ Date 27 7 2012 The termination for the above inputs must be as indicated on the main PCB See page 15 The Earthing of the cable screens...

Page 8: ...x If a grommet is removed fill the hole with a brass cable gland If any knockout is removed but subsequently not used it should be covered up The 230Va c Mains cable must be fed into the enclosure via...

Page 9: ...WER 4 1 CONNECTING THE MAINS POWER Figure 3 Power Supply PCB layout and Mains connection details Figure 3 4 2 CONNECTING THE BATTERIES Figure 4 Battery location and connection details CAUTION RISK OF...

Page 10: ...l screens should be fed through the gland to make electrical contact with it and be terminated at the brass earthing strip as shown below see Figure 6 For detailed detector and alarm circuit wiring di...

Page 11: ...he number with the keypad 0 minutes type nothing 9 minutes type 81 10 minutes type 82 Press 5 The panel will flash a confirmation of the selected delay 6 Press 3 times to exit access level 3 6 3 WIRIN...

Page 12: ...isable one zone at a time 1 Enter access code default 1245 and press 2 Press for 3 seconds 3 Type the number of the zone you want to disable If you wish to disable the sounders press 4 Press to disabl...

Page 13: ...not in test mode at this point 4 Press to start test mode The Zone test LEDs will be flashing with a pattern 12 flashes then a pause repeated The zone is now in test mode 5 To set a different zone int...

Page 14: ...ase that is not making the connection c A short circuit on a zone could be caused by the end of line diode being fitted backwards d Check that the detectors are compatible with this FACP Note that som...

Page 15: ...nect the earth screens one at a time to determine the problem line Note connecting other equipment e g an oscilloscope to the panel can give an earth fault 9 5 SOUNDER FAULTS Similar to the zone fault...

Page 16: ...00005 Amp 50 A Optical Detector 0 0001 Amp 100 A Typical Example A system comprises of 20 ionisation detectors 14 bells and the required standby is 24 hours It will need to operate in alarm for hour...

Page 17: ...bells 10 SND 2 Connect to sounder circuit 2 sirens bells 11 SND 3 Connect to sounder circuit 3 sirens bells 12 SND 4 Connect to sounder circuit 4 sirens bells 13 FAULT RELAY NC CM NO Normally powered...

Page 18: ...TAGE 22 5V DC NOMINAL SOUNDER ALARM OUTPUTS 2 x 150mA 24V DC 1 2 zone panel 4 x 150mA 24V DC 4 6 8 zone panel AUXILIARY FAULT OUTPUT 1 x RELAY SELV 1A MAX AUXILIARY FIRE OUTPUT 1 x RELAY SELV 1A MAX N...

Page 19: ...e condition Giving 2 fire relays Switch 8 ON Makes the last zone on the panel a call point zone alarms from that zone not delayed Note The above options my not comply with local regulations Please che...

Reviews: