INFINITY 8 INSTALLATION MANUAL
Approved Document No. GLT-201-7-1
PAGE 17
Issue: 1.6 Author: NRPJ Date: 27/7/2012
12. PANEL SPECIFICATIONS
12.1 ENCLOSURE SPECIFICATIONS
DESCRIPTION
VALUE
ENCLOSURE SIZE
364 X 302 X 90 mm
TOP CABLE ENTRIES
15 x 20 mm DIA knock outs
12.2 ELECTRICAL SPECIFICATIONS
ELECTRICAL DESCRIPTION
VALUE
MAINS VOLTAGE
100-240V AC +/-10% @ 50/60 Hz
BATTERY VOLTAGE
24V DC (2 X 12V SLA BATTERY)
SYSTEM VOLTAGE
24V DC NOMINAL (18 – 32 V)
SYSTEM VOLTAGE RIPPLE
2V PK-PK MAX
CHARGER SIZE
UP TO 3.4AH in 24 Hours
ZONE VOLTAGE
22.5V DC NOMINAL
SOUNDER ALARM OUTPUTS
2 x 150mA @ 24V DC (1 & 2 zone panel)
4 x 150mA @ 24V DC (4, 6, & 8 zone panel)
AUXILIARY FAULT OUTPUT
1 x RELAY SELV (1A MAX)
AUXILIARY FIRE OUTPUT
1 x RELAY SELV (1A MAX)
NUMBER OF ZONES
1/2/4/6/8
MAXIMUM ZONE CAPACITY
32 DEVICES PER ZONE
SOUNDER ACTIVATION DELAY
0-10 MINUTES - IN 1 MIN INCREMENTS
ZONE END OF LINE DEVICE
1N4002 DIODE (CATHODE STRIPE TO +)
SOUNDER END OF LINE DEVICE
10 K RESISTOR
CHARGER VOLTAGE
28.6V @ 25
o
C (NO BATTERY CONNECTED)
ZONE SHORT CIRCUIT PROTECTION
40mA
CHARGER SHORT CIRCUIT PROTECTION
Batteries less than 20V
TOTAL CHARGER OUTPUT
1.15 Amp
MAX CURRENT DRAIN FROM BATTERY (DURING MAINS FAILURE)
WHEN PSE LOAD IS I MAX A
1.0 Amp
I MAX A
1 Amp
I MAX B
1 Amp
RI MAX
2.8 Ω