What position?

A roof is considered flat unless the height of the apex is greater then 0.6m. If the roof is flat the 
ZetaBeam system can be placed anywhere under the roof between 

0.3m and 0.6m

 below the roof, up to 

a maximum height of 

40m

 from the floor. The ZetaBeam has a detection area of 

7.5m

 either side of the 

beam. If the roof is considered to have an apex, place the ZetaBeam system 

0.3m to 0.6m

 down from 

the top of the apex, up to a maximum height of 

40m

 from the floor. The maximum protected area either 

side of the beam can be extended by 1% for every degree of roof pitch, see the example below:

Warning: 

so that the beam works effectivaly, ensure                                     

the beam is not obstructed in a 1m diameter clear    

 

       line of sight along its entire axis                  

Note

. Careful design consideration should be made when positioning beams and reflectors in 

environments that can be susceptible to condensation i.e. warehouses near to water that have areas 
open to the outside environment or that are exposed to quick extreme changes in temperature. To assist 
with this problem that can affect all beam detectors we produce an 

anti-fog kit

 comprising of a specially 

coated reflector and lens cover. Individual reflectors are also available. The standard ZetaBeam and 
range kits can be supplied as anti-fog sets as a special order.

0.3m - 0.6m

40m max

2.7m min

Field of view should be a 50cm radius from

the centre or the beam 

Flat roof

0.3 -0.6m

15m detection area

Extra coverage due to apex angle

10°

0.3 -0.6m

15 + (15 x 

10%

) = 15m + 1.5m = 16.5m 

16.5m detection area     

8.25m 

8.25m

Min 0.5m

You should always position the beam at least 0.5m away from any protrusion

Wall

Wall

Summary of Contents for Zeta Beam

Page 1: ...The ZetaBeam Protection System Xtra User Guide 0150 01...

Page 2: ...rt range mask supplied on the single reflector 7 to 70 metres the standard ZetaBeam The standard ZetaBeam comes boxed with the head unit low level controller key and quick start installation guide thi...

Page 3: ...t along its entire axis Note Careful design consideration should be made when positioning beams and reflectors in environments that can be susceptible to condensation i e warehouses near to water that...

Page 4: ...ction is not made ERROR will appear on the controller this connection can be checked by reading the resistance across the black and grey terminals they will read 110 ohm if OK or 220 ohm if not connec...

Page 5: ...To re panel To controller EOL FIRE Fire LED Auxiliary no relay contact 2A 30Vdc used for External LED switching no c nc no c nc fault fire controller interface external reset fire technical support 44...

Page 6: ...ne beam To controller Beams 1 2 3 To controller To re panel no c nc no c nc fault fire controller interface external reset fire technical support 44 0 1582 608000 manufactured by Lemtronics Sdn Bhd Ph...

Page 7: ...raw it may be necessary to use normal mode to prevent excessive current draw Fast mode allows x4 times faster motor response and it may be quicker to commission each beam in turn Once commissioning is...

Page 8: ...ill assume it has found the far wall You will need to identify and move the obstruction or reconsider the positioning of the ZetaBeam You can identify that the beam is obstructed by the right hand fig...

Page 9: ...the angle of the beam Y until you receive an AQ of over 100 Re ector is lower than the beam head use Y to bring the beam onto the re ector Beam head Re ector y x x y Manual AQ 125 X 0 000 Y 0 000 Manu...

Page 10: ...and would normally be below 0 90 If this is not the case you may need to start the Manual Alignment process again to return both the zetabeam axis to 0 00 and identify and remove the obstruction Air Q...

Page 11: ...ding the resistance across the black and grey terminals if connected it should read 110ohms if not connected at one end this will read 220ohms This screen will appear when the beam is performing a sel...

Page 12: ...o return signal is received the beam will reach full power and the screen will say Pre Align complete If you don t receive high enough output power and receiver sensitivity readings this will usually...

Page 13: ...uto reset The beam is factory set to auto reset when the received signal raises above the fire threshold hysteresis This can be set to latching if your system requires this Change by using the right a...

Page 14: ...before it returns to normal This action prevents small fluctuations in returned signal causing the beam to fall in and out of a fire state This can be adjusted between 1 and 40 by using the right and...

Page 15: ...g needs to be maintained in the beam path use the right and left keys to turn the system on and off This will show as a fault on the panel Press enter to return to beam maintenance 5 Press enter to go...

Page 16: ...s Electrical Specifications Supply Voltage 12 to 30 VDC Supply Current 3 5mA constant current in all operational states Constant Current 17mA constant current in fast commissioning Environmental Speci...

Reviews: