Green flashing light on / off

. By using the 

right

 and 

left

 keys you can turn the green 

flashing LED, located on the head and controller, 

on

 or 

off

. This is a useful way of 

identifying the beam head you are working with (press 

enter

 to return to 

mode 

change

 or 

down

 to go to 

phase

).

Phase

. When using multiple beams that face each other the beam output signals could 

phase together and can cause unreliable readings, by setting each beam to phase 

differently alleviates this problem. Use the 

right

 and 

left

 keys to give each beam a 

different phase pattern (length between output beam sample times) you can choose 

between 

0 (default setting)

 and 

6

 (press 

enter

 to return to 

mode change

 or 

down

 to 

go to 

hysteresis

).

Hysteresis

. Changing the 

hysteresis

 will change the delay in returning from a 

fire

 state 

back to a 

normal

 state, for example, the beam is factory set at 15% so if the beam 

falls into fire at 65% (35% threshold) it has to recover 15% to 80% before it returns 

to normal. This action prevents small fluctuations in returned signal causing the 

beam to fall in and out of a fire state. This can be adjusted between 

1%

 and 

40%

 by 

using the 

right

 and 

left

 keys (press 

enter

 to return to 

mode change

 or 

down

 to go to 

compensation fire / fault

).

4. Press 

enter

 to go into 

beam maintenance

.

Dirt Comp

. This screen shows how much the beam has compensated for dust build-

up on the beam head and reflectors, 

ALWAYS

 take a note of this value as part of your 

routine maintenance to see any build-up pattern, if you see figures above 

+50%

 you 

should clean both the lens face and the reflectors (once cleaned you should instigate 

an 

auto alignment 

to re-calibrate the beams settings).

It is possible that you may see a negative number here, this can happen when the 

ZetaBeam has been commissioned in a ‘dirty’ atmosphere such as builders dust which, 

once cleared, the beam then compensates for. To reset, perform an 

auto alignment

 to 

re-calibrate the beam (press 

enter

 to return to 

beam maintenance

 or 

down

 to go to 

event counts

).

Green Flashing 

Light On/Off

Phase

Hysteresis

Beam Maintenance

Dirt Comp

enter

Summary of Contents for Zeta Beam

Page 1: ...The ZetaBeam Protection System Xtra User Guide 0150 01...

Page 2: ...rt range mask supplied on the single reflector 7 to 70 metres the standard ZetaBeam The standard ZetaBeam comes boxed with the head unit low level controller key and quick start installation guide thi...

Page 3: ...t along its entire axis Note Careful design consideration should be made when positioning beams and reflectors in environments that can be susceptible to condensation i e warehouses near to water that...

Page 4: ...ction is not made ERROR will appear on the controller this connection can be checked by reading the resistance across the black and grey terminals they will read 110 ohm if OK or 220 ohm if not connec...

Page 5: ...To re panel To controller EOL FIRE Fire LED Auxiliary no relay contact 2A 30Vdc used for External LED switching no c nc no c nc fault fire controller interface external reset fire technical support 44...

Page 6: ...ne beam To controller Beams 1 2 3 To controller To re panel no c nc no c nc fault fire controller interface external reset fire technical support 44 0 1582 608000 manufactured by Lemtronics Sdn Bhd Ph...

Page 7: ...raw it may be necessary to use normal mode to prevent excessive current draw Fast mode allows x4 times faster motor response and it may be quicker to commission each beam in turn Once commissioning is...

Page 8: ...ill assume it has found the far wall You will need to identify and move the obstruction or reconsider the positioning of the ZetaBeam You can identify that the beam is obstructed by the right hand fig...

Page 9: ...the angle of the beam Y until you receive an AQ of over 100 Re ector is lower than the beam head use Y to bring the beam onto the re ector Beam head Re ector y x x y Manual AQ 125 X 0 000 Y 0 000 Manu...

Page 10: ...and would normally be below 0 90 If this is not the case you may need to start the Manual Alignment process again to return both the zetabeam axis to 0 00 and identify and remove the obstruction Air Q...

Page 11: ...ding the resistance across the black and grey terminals if connected it should read 110ohms if not connected at one end this will read 220ohms This screen will appear when the beam is performing a sel...

Page 12: ...o return signal is received the beam will reach full power and the screen will say Pre Align complete If you don t receive high enough output power and receiver sensitivity readings this will usually...

Page 13: ...uto reset The beam is factory set to auto reset when the received signal raises above the fire threshold hysteresis This can be set to latching if your system requires this Change by using the right a...

Page 14: ...before it returns to normal This action prevents small fluctuations in returned signal causing the beam to fall in and out of a fire state This can be adjusted between 1 and 40 by using the right and...

Page 15: ...g needs to be maintained in the beam path use the right and left keys to turn the system on and off This will show as a fault on the panel Press enter to return to beam maintenance 5 Press enter to go...

Page 16: ...s Electrical Specifications Supply Voltage 12 to 30 VDC Supply Current 3 5mA constant current in all operational states Constant Current 17mA constant current in fast commissioning Environmental Speci...

Reviews: