Event counts.

 Here we can see how many times the beam has gone into 

fire

 or 

fault

 

since the beam was commissioned or since the event log was last cleared.

Press 

enter

 

to 

clear events.

Press 

left/back

 

to return to 

beam maintenance

 or 

down

 to go to 

self test

.

Self test

Press 

enter

 

to perform a 

fire test

, this works by running a test algorithm to 

lower the 

output power, the receiver sees this as obscuration. When the 

received signal drops below the threshold point the beam will trip the 

fire

 relay – this 

relay will not trip until the 

time to fire

 has passed which could be anything between 

2

 

and 

30 seconds

Press 

left / back

 

to end test, the 

fire

 test should show on the panel. Press 

left 

/ back

 to return 

to 

beam maintenance

 or 

down

 to go to 

on / off

.

On / off

. If something needs to be maintained in the beam path use the 

right

 and 

left

 

keys to turn the system 

on

 and 

off

.

This will show as a 

fault

 on the panel. 

Press 

enter

 

to return to 

beam maintenance

.

5. Press 

enter

 

to go into 

diagnostics

.

IR power

. This screen shows the amount of output power that is being transmitted. It 

can be increased or decreased by using the 

right

 and 

left

 keys (press 

enter

 to return 

to 

diagnostics

 or 

down

 to go to 

RX sensitivity

).

RX sensitivity

. This screen shows the receiver sensitivity and can be changed by 

using the 

right

 and 

left

 keys (press 

enter

 to return to 

diagnostics

 or 

down

 to go to 

temperature

).

Temperature

. Here we can see the temperature at the beam head and the amount of 

compensation being made for temperature (no adjustments can be made here).

Press 

enter

 

to return to 

diagnostics

.

Alarm & Fault

Event Counts

Self Test

On / Off

Diagnostics

IR Power

RX Sensitivity

Temperature

Temp Comp XX%

enter

enter

enter

enter

enter

enter

left/

back

left/

back

Summary of Contents for Zeta Beam

Page 1: ...The ZetaBeam Protection System Xtra User Guide 0150 01...

Page 2: ...rt range mask supplied on the single reflector 7 to 70 metres the standard ZetaBeam The standard ZetaBeam comes boxed with the head unit low level controller key and quick start installation guide thi...

Page 3: ...t along its entire axis Note Careful design consideration should be made when positioning beams and reflectors in environments that can be susceptible to condensation i e warehouses near to water that...

Page 4: ...ction is not made ERROR will appear on the controller this connection can be checked by reading the resistance across the black and grey terminals they will read 110 ohm if OK or 220 ohm if not connec...

Page 5: ...To re panel To controller EOL FIRE Fire LED Auxiliary no relay contact 2A 30Vdc used for External LED switching no c nc no c nc fault fire controller interface external reset fire technical support 44...

Page 6: ...ne beam To controller Beams 1 2 3 To controller To re panel no c nc no c nc fault fire controller interface external reset fire technical support 44 0 1582 608000 manufactured by Lemtronics Sdn Bhd Ph...

Page 7: ...raw it may be necessary to use normal mode to prevent excessive current draw Fast mode allows x4 times faster motor response and it may be quicker to commission each beam in turn Once commissioning is...

Page 8: ...ill assume it has found the far wall You will need to identify and move the obstruction or reconsider the positioning of the ZetaBeam You can identify that the beam is obstructed by the right hand fig...

Page 9: ...the angle of the beam Y until you receive an AQ of over 100 Re ector is lower than the beam head use Y to bring the beam onto the re ector Beam head Re ector y x x y Manual AQ 125 X 0 000 Y 0 000 Manu...

Page 10: ...and would normally be below 0 90 If this is not the case you may need to start the Manual Alignment process again to return both the zetabeam axis to 0 00 and identify and remove the obstruction Air Q...

Page 11: ...ding the resistance across the black and grey terminals if connected it should read 110ohms if not connected at one end this will read 220ohms This screen will appear when the beam is performing a sel...

Page 12: ...o return signal is received the beam will reach full power and the screen will say Pre Align complete If you don t receive high enough output power and receiver sensitivity readings this will usually...

Page 13: ...uto reset The beam is factory set to auto reset when the received signal raises above the fire threshold hysteresis This can be set to latching if your system requires this Change by using the right a...

Page 14: ...before it returns to normal This action prevents small fluctuations in returned signal causing the beam to fall in and out of a fire state This can be adjusted between 1 and 40 by using the right and...

Page 15: ...g needs to be maintained in the beam path use the right and left keys to turn the system on and off This will show as a fault on the panel Press enter to return to beam maintenance 5 Press enter to go...

Page 16: ...s Electrical Specifications Supply Voltage 12 to 30 VDC Supply Current 3 5mA constant current in all operational states Constant Current 17mA constant current in fast commissioning Environmental Speci...

Reviews: