Smart Connect Multi-loop Installation Manual
www.zetaalarmsystems.com
40
Status LED’s
The status of the device is shown via visual feedback. The status LED identifies the hardware status of the printer. The table below
shows the various LED signals and their corresponding status.
Status LED
LED Colour
Description
OFF
Green
Printer is off
ON
Green
Printer is on: No error
ON Flash x 2
Green
Printer head over temperature
ON Flash x 3
Green
Printer paper empty
ON Flash x 4
Green
Power supply voltage is incorrect
ON Flash x 5
Green
Reception errors (Parity, frame error, overrun error)
ON Flash x 6
Green
Command is not recognised
ON Flash x 7
Green
Command reception has timed out
Printer Maintenance
The regular cleaning of the panel printer will help maintain its print quality and extend its lifetime. The table below shows the
recommended maintenance timeline and cleaning operations.
Every Paper Change
Printer Head
Use Isopropyl Alcohol
Rollers
Use Isopropyl Alcohol
Every 5 Paper Changes
Paper Path
Use Compressed Air
Sensors
Use Compressed Air
Every 6 Months or as Needed
Printer Case
Use Compressed Air or a Soft Cloth
Note:
If the SMART Connect Multi-loop panel is installed in a dusty environment, the
times between the cleaning operations should be reduced.