Smart Connect Multi-loop Installation Manual
www.zetaalarmsystems.com
15
Figure 3: Wiring the mains power supply
Panel
Input Voltage Input
Frequency
PSU Cage
Size
Max Input Current
Max Surge current
Fuse
Installed
SMART6
120-230V AC
47-63 Hz
400W
3.6Amax@120Vac & Full-Load,
2.0Amax@220Vac & Full-Load
65A peak, 1.2ms duration,
<0.25A2s@230Vac, Cold Start
3.15A (230
V AC)
SMART10 120-230V AC
47-63 Hz
400W
3.6Amax@120Vac & Full-Load,
2.0Amax@220Vac & Full-Load
65A peak, 1.2ms duration,
<0.25A2s@230Vac, Cold Start
3.15A (230
V AC)
SMART26 120-230V AC
47-63 Hz
400W
3.6Amax@120Vac & Full-Load,
2.0Amax@220Vac & Full-Load
65A peak, 1.2ms duration,
<0.25A2s@230Vac, Cold Start
3.15A (230
V AC)
Battery Wiring
The SMART Connect Multi-loop panel uses two 12 Volt batteries, wired in series to give a 24 Volt back-up supply.
The
+ve
of one battery is connected to the
red
battery lead.
The
–
ve
of the other battery is connected to the
black
battery lead.
The
–
ve
of the first battery is connected to the
+ve
of the second battery using the link wire supplied.
Recommended Battery Types:
Panel
Recommended Battery size
SMART6
2 x Powersonic 12V,14Ah
SMART10
2 x Powersonic 12V,38Ah
SMART26
2 x Powersonic 12V,38Ah
To calculate the required backup battery capacity, use the information in Appendix B
Other makes and sizes of battery may be suitable. Calculate the standby requirements to determine the most suitable size of batteries.
Figure 4: Battery location and connection