Smart Connect Multi-loop Installation Manual
www.zetaalarmsystems.com
42
FUNCTIONS REQUIRED BY EUROPEAN STANDARD EN54-2
The Smart Connect Multi-loop fire alarm control panel provides the following mandatory and optional functions as prescribed by the
European standard EN54-2.
(a)
Mandatory Functions
The mandatory functions and corresponding indications provided by this panel are:
•
Fire alarm condition
•
Fault warning condition
•
Disablement condition
•
Quiescent condition (when the CIE is powered by a power supply conforming to EN 54-4 and no other functional
condition is indicated)
(b)
Optional Functions (Options with Requirements)
The options with requirements provided by this panel are:
•
Clause 7.8
–
Output to fire alarm device(s)
•
Clause 7.11
–
Delays to outputs
•
Clause 7.12.2
–
Dependencies on more than one alarm signal - Type B
•
Clause 7.12.3
–
Dependencies on more than one alarm signal - Type C
•
Clause 8.3
–
Fault signals from points
•
Clause 9.5
–
Disablement of each address points
•
Clause 10
–
Test Condition
(c)
Other Functions outside EN54
•
USB port (For PC configuration and software upgrading)
•
RS485 Network / Repeater connection
•
TCP/IP (Ethernet) connection (Remote access)
•
Programmable Cause / Effect on Outputs (Phased Evacuation)
•
Printer Option
•
Auxiliary Power Supply Output (via SCM-ACM)
•
Auxiliary Relay Outputs
FUNCTIONS REQUIRED BY EUROPEAN STANDARD EN54-4
The Smart Connect Multi-loop fire alarm control panel provides the following mandatory functions as prescribed by the European
standard EN54-4.
(a)
Mandatory Functions
The mandatory functions and corresponding indications provided by this panel are:
•
Clause 5.1
–
Power supply from the main power source
•
Clause 5.2
–
Power supply from the standby power source (battery)
•
Clause 5.3
–
Charger
•
Clause 5.4
–
Faults
Appendix B: STANDBY BATTERY REQUIREMENTS
A spreadsheet is available for calculating the standby battery requirements. The table below is provided for information:
Model Number
Description
Standby Current (mA)
(Mains Fail Condition)
Alarm Current (mA)
SMART6
Smart Connect Multi-loop 6 expansion port FACP
110
SMART10
Smart Connect Multi-loop 10 expansion port FACP
112
SMART26
Smart Connect Multi-loop 26 expansion port FACP
120
SCM-LCM
Loop Card Module
87*
87*