ZoningBOX 6 / ZoningBOX 4
Technical Support:
30
Note
:
enabling the last two options together (status and status requests) may cause
contradictory situations if their delays are not properly configured. It is advisable to
send the status requests prior to any other sending
.
ETS PARAMETERISATION
The Reset tab (available by default after enabling the Zoning function from the General
tab; see section 2.1) provides the following parameters:
Figure 23.
Zoning - Reset
Send Grilles Control Objects After Reset
[
disabled
/enabled
]: sets whether
the grille control objects should be sent to the KNX bus after a reset.
➢
Delay
[
0
…255 s
]: time before sending the objects, after the start-up.
Send Status to HVAC Unit After Reset
[
disabled
/enabled
]: sets whether the
status objects of the HVAC unit should be sent to the KNX bus after a reset.
➢
Delay
[
0
…255 s
]: time before sending the objects, after the start-up.
Status Request After Reset
[
disabled
/enabled
]: sets whether to send or not
the status reading requests to the KNX bus after the reset.
➢
Delay
[
0
…255 s
]: time before sending the objects, after the start-up.