ANNEX I. COMMUNICATION OBJECTS
“Functional range
” shows the values that, with independence of any other values permitted by the bus according to the object size, may be of any use or have a
particular meaning because of the specifications or restrictions from both the KNX standard or the application programme itself.
Number
Size
I/O
Flags
Data Type (DPT)
Functional Range
Name
Function
1
1 Bit
C T - - -
DPT_Trigger
0/1
[Heartbeat] Object to Send '1'
Sending of '1' Periodically
2
1 Bit
C T - - -
DPT_Trigger
0/1
Reset 0
Voltage Recovery -> Sending 0
3
1 Bit
C T - - -
DPT_Trigger
0/1
Reset 1
Voltage Recovery -> Sending 1
4
1 Bit
I
C - - W -
DPT_Enable
0/1
Manual Control Lock
0 = Lock; 1 = Unlock
1 Bit
I
C - - W -
DPT_Enable
0/1
Manual Control Lock
0 = Unlock; 1 = Lock
5, 6, 7, 8, 9, 10, 11,
12, 13, 14, 15, 16,
17, 18, 19, 20, 21,
22, 23, 24, 25, 26,
27, 28, 29, 30, 31,
32, 33, 34, 35, 36
1 Bit
I
C - - W -
DPT_Bool
0/1
[LF] (1-Bit) Data Entry x
Binary Data Entry (0/1)
37, 38, 39, 40, 41,
42, 43, 44, 45, 46,
47, 48, 49, 50, 51, 52
1 Byte
I
C - - W -
DPT_Value_1_Ucount
0 - 255
[LF] (1-Byte) Data Entry x
1-Byte Data Entry (0-255)
53, 54, 55, 56, 57,
58, 59, 60, 61, 62,
63, 64, 65, 66, 67, 68
2 Bytes
I
C - - W -
DPT_Value_2_Ucount
0 - 65535
[LF] (2-Byte) Data Entry x
2-Byte Data Entry
DPT_Value_2_Count
-32768 - 32767
DPT_Value_Temp
-273,00 -
670760,00
69, 70, 71, 72, 73,
74, 75, 76
4 Bytes
I
C - - W -
DPT_Value_4_Count
-2147483648 -
2147483647
[LF] (4-Byte) Data Entry x
4-Byte Data Entry
77, 78, 79, 80, 81,
82, 83, 84, 85, 86
1 Bit
O
C T R - -
DPT_Bool
0/1
[LF] Function x - Result
(1-Bit) Boolean
1 Byte
O
C T R - -
DPT_Value_1_Ucount
0 - 255
[LF] Function x - Result
(1-Byte) Unsigned
2 Bytes
O
C T R - -
DPT_Value_2_Ucount
0 - 65535
[LF] Function x - Result
(2-Byte) Unsigned
4 Bytes
O
C T R - -
DPT_Value_4_Count
[LF] Function x - Result
(4-Byte) Signed
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
[LF] Function x - Result
(1-Byte) Percentage
2 Bytes
O
C T R - -
DPT_Value_2_Count
-65535
[LF] Function x - Result
(2-Byte) Signed
2 Bytes
O
C T R - -
DPT_Value_Temp
-273.00 ºC -
670760.00 ºC
[LF] Function x - Result
(2-Byte) Float
87
1 Byte
I
C - - W -
DPT_SceneControl
0-63; 128-191
[Outputs] Scenes
0 – 63 (Execute 1 – 64); 128 – 191
(Save 1 – 64)