Fan Coil ‘Analog’
Technical Support:
15
Initial Status
[
Previous
/ Off
].
If “Previous” is selected, the status before the failure
status shall be maintained, except after programming, in which case the output
will be off.
Input Objects Update
[
disabled
/enabled
]: if enabled, a reading of the input
objects will be carried out after a bus fault or ETS download. The read requests
will start to be sent after the parameterized
delay
([
0
...600
][
s
]).
Send Status Object
[
disabled
/enabled
]: if enabled, several checkboxes will be
displayed to indicate the objects to be sent.
➢
On/Off
[
disabled
/enabled
]. Available if the
Fan Coil Always On
parameter
(section 2.2) is disabled.
➢
Mode
[
disabled
/enabled
]. Available if the selected
type of fan coil
is "4
Pipes" or "2 Pipes" with the "C Heating"
mode
active (see section
➢
Fan: Automatic/Manual
[
disabled
/enabled
]. Available if the fan
control
mode
selected for the fan is "Aut Manual" (see section 2.2.2).
The statuses will start to be sent after the parameterized
delay
[
0
...600
][
s
].