Fan Coil ‘Analog’
Technical Support:
14
2.2.3
INITIALISATION
The fan coil
‘Analog’ function module after ETS download, and for safety reasons, will
always initialise off. After a bus failure the module, by default, will keep its previous state.
This tab offers the possibility to configure the initialization of the Fan Coil 'Analog' module
by defining aspects such as its initial state or whether an update of the input objects
and/or the sending of certain status objects is required after start-up.
If the
input objects update
functionality is enabled, the objects on which read requests
for update will be sent will be:
"[FCx] On/Off".
"[FCx] Mode".
"[FCx] Control Variable (Heating/Cooling)".
"[FCx] Fan: Manual/Automatic".
"[FCx] Manual Fan: Speed".
"FCx] Manual Fan: Manual Control Duration".
If, for the purpose of updating other devices in the system the
status sending
start-up
is enabled, the available status objects can be additionally selected to be sent:
"[FCx] On/Off (status)".
"FCx] Mode (status)".
"FCx] Fan: Manual/Automatic (Status)".
ETS PARAMETERISATION
After selecting the "Custom" option, in the
Initialization
parameter, in the "Fan Coil X"
tab (see section 2.2), a new tab of the same name is added to the left tree.
Figure 7.
Fan Coil - Initialization.