Zenith Hydro Tap Installation and Operating Instructions - 81467 - February 2005

Installation procedure 

continued

Vent line 

Chilled line 

Hot line 

Front

Vent

Hot Outlet

Step B - Installing the undersink unit (all models)
SPECIAL NOTE: The HydroTap undersink units are heavy, take note of the
weights listed in the table on page 4. If you think you cannot lift the unit
safely, get help and avoid possible injury.

Before positioning the heater connect the braided water inlet hose (supplied) to the
cold water inlet on the unit. This is located at the rear of the unit.

Position the Zenith HydroTap undersink unit as close as possible to directly beneath
the Zenith HydroTap tap head.

The connection tubes supplied with the tap head assembly CANNOT be lengthened.

Leave at least a 50 mm air-gap without obstruction on each side of the unit.

Adjust both cupboard door hinges and attach the supplied rubber door buffers to
the doors to create a 4 mm air-gap between the doors and the cupboard. This is
the minimum ventilation requirement for low usage installations.

Important Note:

Proper air circulation must be provided for all Boiling and Chilled

models. The system will operate correctly only if the recommended air gaps are
achieved during installation. A ventilation hole measuring 100mm must be cut into
the top half of the cupboard door to accommodate the air vent provided. Make
sure that the undersink unit ventilation grilles are not obstructed in any way.

This instruction is critical!

Cupboard ventilation for Boiling only and Boiling Ambient models is recommended
but not essential.

Step C - Connecting the tap
Model BC and HT (boiling/chilled models)

Measure and trim the blue tube and connect it to the chilled water outlet located on 
the top front, right hand side of the nder-sink unit. Use spring clamps provided.

Measure and trim the red marked tube and connect it to the hot water outlet
located on the top center, right hand side of the undersink unit. Use spring clamps
provided.

Measure and trim the unmarked tube and connect it to the vent outlet located on
the top center, left hand side the top of the undersink unit.Use spring clamps
provided.

NOTE:

All tubes must have a continuous fall back to the undersink unit.

Connect the tap USB connector to the USB connector attached to the undersink
unit. Orient the USB plug carefully and connect, do not force the plug. Once
connected, fix the cable to the wall, ensure it is away from any possible water
splashes and is off the floor.

Note:

When trimming any silicon tubes trim to minimum length, do not loop any

excess or allow kinking of the tubes. When connecting, slide the tube over the pipe
at least 25mm.

Model B, BD and HT (boiling only models)

Measure and trim the red marked tube and / or the blue marked tube and connect
it to the hot water outlet and amblient outlet if a BD model, on the top of the
undersink unit. Use spring clamps provided.

Measure and trim the unmarked tube and connect it to the vent outlet on the top of
the undersink unit. Use spring clamps provided.

NOTE: 

All tubes must have a continuous fall back to the undersink unit.

Connect the tap USB connector to the USB connector attached to the undersink
unit. Orient the USB plug carefully and connect, do not force the plug. Once
connected, fix the cable to the wall, ensure it is away from any possible water
splashes and is off the floor.

Summary of Contents for HYDROTAP 30009

Page 1: ...droTap Filtered boiling and chilled drinking water for kitchens and tea rooms Commercial Models 30281 Zenith HydroTap BC150 175 30271 Zenith HydroTap BC100 125 37201 Zenith HydroTap B10OF 38201 Zenith...

Page 2: ...all models 7 Step E Testing and commissioning 7 Font Installation procedure 8 Operating the Tap 9 Cleaning 10 Replacing the Filter 10 Pull out Font Template pages a b c d Setting the Energy Saver Tim...

Page 3: ...e given in the table under the heading Installation Requirements Do not lift the unit by the doors Airflow The ambient temperatures this unit should operate within are 5 C 35 C Proper air circulation...

Page 4: ...750 mm flexible connection and positioned so that the connection point and the stop cock will not be obstructed when the undersink unit is installed Power supply 220 240 Volt AC for connection to the...

Page 5: ...lide it up to meet the All Thread and pass the All Thread through the center of the Spider Clamp 7 Hold the All Thread steady and re fit the 6mm nut to the All Thread using the tube spanner supplied i...

Page 6: ...essential Step C Connecting the tap Model BC and HT boiling chilled models Measure and trim the blue tube and connect it to the chilled water outlet located on the top front right hand side of the nde...

Page 7: ...e water to 95 C maintaining it at that temperature for a short stabilization period Once stabilized the element will cycle On bring the water to boiling point and hold it there for a short period The...

Page 8: ...e fixing nut withtheTube Spanner provided in the kit NOTE The All Thread is a floating component it locks into place once tension is applied by the fixing nut and washer 6 Tighten the securing pin so...

Page 9: ...he Blue lever allows dispensing of chilled water Pulling up the Blue lever allows the tap to operate in a no touch mode Water will flow for a maximum time of 15 seconds To reset return the handle to t...

Page 10: ...il it stops 4 Ease cartridge downwards to detach it from the filter head socket 5 Do not tilt the cartridge as dirty water may spill from it if tilted 6 Unpack replacement cartridge and write today s...

Page 11: ...ions section of this document Press either Mode or Mode button until Litres Filtered is displayed Press Adjust once and Reset Counter will be displayed press Adjust button once and Are You Sure will b...

Page 12: ...is the most effective for your installation Application of the fan is of paramount importance in situations where the cupboard space reaches temperatures greater than 35 C Boiling Water Safety Isolati...

Page 13: ...ust come out of OFF cycle Possible internal fault Excessive use unit refilling or chilling down to temperature Possible internal fault Check power supply Ensure power plug is correctly fitted and swit...

Page 14: ...tor kit BC150 175 17 Z90023 compressor kit BC150 175 7 Z90633 sensor probe kit 18 Z90639 fan motor kit BC100 125 8 Z90634 pump kit cold 18 Z90640 fan motor kit BC150 175 9 Z90622 PCB kit BC100 125 BC1...

Page 15: ...kit hot tank BC100 125 4 Z90617 gasket and elbow kit BC 150 175 16 Z90630 level sensor kit hot tank BC150 175 5 Z90579 overload kit 17 Z90186 loom overlad kit 6 Z90618 element 1500W kit 18 Z90187 loom...

Page 16: ...e Solenoid Kit 4 Z90658 Gasket and Elbow Kit BC 100 125 5 Z90579 Overload Kit 6 Z90618 Element 1500 watt Kit 7 Z90620 Sensor Probe Hot 8 Z90621 Pump Kit Hot 9 Z90689 PCB Kit Boiling Only 10 Z90624 Lea...

Page 17: ...Zenith Hydro Tap Installation and Operating Instructions 81467 February 2005 Page 17 of 20 Notes...

Page 18: ...Page 18 of 20 Zenith Hydro Tap Installation and Operating Instructions 81467 February 2005 Notes...

Page 19: ...Zenith Hydro Tap Installation and Operating Instructions 81467 February 2005 Page 19 of 20 Notes...

Page 20: ...osts are payable by the customer other than any mileage or travelling time charges incurred by a Zenith Service Provider or the cost of removal cartage and re installation of any component of the appl...

Reviews: