Zehnder Rittling RW Series Installation, Operation And Maintenance Manual Download Page 6

Standard ratings and specifications

Table A

Specifications

02

03

04

06

08

10

12

Steam capacity

MBH

18.7

25.5

34.8

51.0

62.8

73.4

90.7

EDR

76

104

144

212

260

304

376

Hot water capacity  

(1 row coil)

MBH

16.2

22.4

30.7

45.5

54.8

64.5

80.1

GPM

1.7

2.3

3.2

4.8

5.7

6.7

8.4

WPD

0.2

0.4

0.8

2.2

0.5

0.7

1.2

Hot water capacity  

(2 row coil)

MBH

25.0

34.3

47.2

69.5

86.6

101.2

125.8

GPM

2.6

3.6

4.9

7.3

9.0

10.5

13.1

WPD

0.8

1.7

3.6

9.3

2.2

3.3

5.6

CFM: standard

High

220

300

420

620

810

940

1180

Medium

150

200

310

450

600

720

875

Low

125

140

220

350

440

480

660

CFM: high static  

(@ 0.2" ESP)

High

250

345

490

640

920

1020

1150

Medium

210

290

425

550

780

870

980

Low

160

230

320

420

590

660

750

Coil

FPI

12

12

12

12

12

12

12

Face area, ft2

1.25

1.67

2.08

2.92

3.33

3.89

4.58

Coil connections

1/2" Cu

1/2" Cu

1/2" Cu

1/2" Cu

1/2" Cu

1/2" Cu

1/2" Cu

Blower

Quantity

1

1

2

2

1, 2

4

4

Diameter

5.7"

5.7"

5.7"

5.7"

5.7"

5.7"

5.7"

Width

7.5"

10.4"

7.5"

10.4"

7.5", 10.4"

7.5"

10.4"

Filter

Number

1

1

1

1

1

1

1

Length, in.

22

28

34

46

52

60

70

Width, in. - standard

9.75

9.75

9.75

9.75

9.75

9.75

9.75

Width, in. - floor with inlet grille

7.25

7.25

7.25

7.25

7.25

7.25

7.25

Rating

Merv 4

Merv 4

Merv 4

Merv 4

Merv 4

Merv 4

Merv 4

Thickness, in.

1

1

1

1

1

1

1

Cabinet size

Length, in.

38.2

44.2

50.2

62.2

68.2

76.2

86.2

Width, in.

10

10

10

10

10

10

10

Height, in. - wall/ceiling

24

24

24

24

24

24

24

Height, in. - flat top floor

26.5

26.5

26.5

26.5

26.5

26.5

26.5

Height, in. - slope top floor

29.25

29.25

29.25

29.25

29.25

29.25

29.25

Shipping weight, lbs.

85

100

115

140

155

170

195

Notes

 

„

Airflows for floor mounted units with 1-row coil. Please check with factory 
for adjusted outputs on other models

 

„

Heating capacity based on inlet air 60 ˚F DB, 200˚F entering water or 2 psig 
steam, 180˚F leaving water, standard motor at high fan speed

 

„

Pressure drop (PD) shown in feet of water

 

„

Overall length for fully and partially recessed units is 3", adding 
in the trim kit. Wall rough-in hole dimension to be 1/2" by 24-1/2" 
minimum. Maximum opening to be length by +2" by 26".

STANDARD RATINGS 

4

Summary of Contents for RW Series

Page 1: ...Installation Operations and Maintenance Rittling Cabinet Unit Heater Hydronic Heating Radiant Ceiling Systems...

Page 2: ...you will find the perfect climate for any space www zehnder systems com IMPROVED QUALITY OF LIFE Zehnder decorative radiators Comfortable indoor ventilation Heating and cooling ceiling systems Clean a...

Page 3: ...fety considerations 14 Unpacking and preparation 15 Handling and installation 16 Hot water connections 17 Ductwork connections 18 Electrical connections 19 Wiring diagram 20 Start up 22 Air system bal...

Page 4: ...ilable RWI Wall inverted flow RWI 290 shown RWI 300 and RWI 310 available RRW 320 RRW Wall partially recessed RRW 320 shown RRWI 330 RRWI Wall partially recessed inverted flow RRWI 330 shown RFRW 340...

Page 5: ...or RF 200 shown RF 220 available RC Ceiling RC 360 shown RC 370 RC 380 RC 390 and RC 400 available RFI 240 RFI 250 RFI Floor inverted flow RFI 240 shown RFI 250 available RS 200 RS Floor sloped RS 200...

Page 6: ...4 7 5 10 4 7 5 10 4 7 5 10 4 Filter Number 1 1 1 1 1 1 1 Length in 22 28 34 46 52 60 70 Width in standard 9 75 9 75 9 75 9 75 9 75 9 75 9 75 Width in floor with inlet grille 7 25 7 25 7 25 7 25 7 25 7...

Page 7: ...240 250 High Static 117 120 130 180 325 368 368 ECM Standard 38 38 45 80 125 147 157 Electrical data Notes Maximum circuit ampacity MCA 1 25 x FLA motor 1 FLA motor 2 FLA electric heat Maximum overcur...

Page 8: ...2 3 4 row hot water return Side view Model RF position Filter 1 row hot water return 2 3 4 row hot water supply Front view Front outlet A 6 3 1 2 3 26 1 2 Models RF and RFI Dimensions and data Dimens...

Page 9: ...11 16 4 7 16 3 Row 19 1 16 3 1 16 20 3 8 4 13 16 8 9 16 4 13 16 9 7 8 3 1 16 4 Row 19 1 16 3 1 16 20 3 8 4 13 16 8 9 16 4 13 16 9 7 8 3 1 16 Notes 1 2 3 and 4 row coil supply and return 1 2 nominal 5...

Page 10: ...nal 5 8 OD all sizes Left hand piping connections shown right hand electrical as standard Piping hand determined when facing the air outlet Unit length for 6 extended end pocket add 6 to dimension A A...

Page 11: ...imensions and data Dimensional data Unit size A B C Louvers Duct opening Std 6 Ext D E F G 02 38 3 16 44 3 16 22 3 16 23 5 8 20 6 18 3 16 5 1 8 03 44 3 16 50 3 16 28 3 16 29 5 8 26 6 24 3 16 5 1 8 04...

Page 12: ...46 3 8 48 23 5 8 08 68 3 16 52 3 8 54 33 5 8 10 76 3 16 60 3 8 62 33 5 8 12 86 3 16 70 3 8 72 33 5 8 Notes Damper motor always on right side when viewing unit from front side All listed dimensions are...

Page 13: ...ouvered inlet grille with internal bug screen 3 1 2 A Front View Weep holes 2 5 8 4 to 8 1 2 2 13 16 Side View Dimensional data Model A Rough opening WB 0203 24 22 1 2 x 3 WB 0406 29 27 1 2 x 3 WB 081...

Page 14: ...artially recessed units locate frame as needed Use sheet metal screws by others to secure trimframe to the unit Dimensional data Unit size A H 02 38 3 16 41 3 16 03 44 3 16 47 3 16 04 50 3 16 53 3 16...

Page 15: ...ding must be reported to the shipping company within 15 days of receipt of the shipment All units are shipped F O B factory Therefore Zehnder Rittling is not responsible for damage during transit It i...

Page 16: ...f all authorities having jurisdiction and must conform to all applicable codes Only trained and qualified service personnel using good judgment and safe practices should install repair and or service...

Page 17: ...d container exterior carefully remove each unit from the container and inspect for hidden damage At this time check that all shipped loose items such as wall mounted thermostats aquastats remote tempe...

Page 18: ...s a matter of choice however the mounting point should always be that provided in the chassis or cabinet Improper mounting could result in the unit falling from its position causing personal injury or...

Page 19: ...union nut hand tight and then tighten no more than an additional 1 4 turn The inlet supply connection is marked at the appropriate coil stub out with the other coil stub out being the outlet return c...

Page 20: ...ave some form of low temperature protection to prevent coil s from freezing This protection may be a low temperature thermostat to close the outside air damper a preheat coil to temper the outside air...

Page 21: ...ould result in personal injury or damage to components and will void the manufacturer warranty All wiring connections should be checked prior to start up to ensure connections have not come loose duri...

Page 22: ...D 16AWG WIRE TERMINATION FACTORY WIRE NOT CONNECTED WIRE CONNECTION FIELD WIRED FACTORY WIRED 18AWG FACTORY WIRED 12AWG Blower motor wiring chart Size Motor Sizes High Medium Low 02 12W Black Blue Red...

Page 23: ...ED FACTORY WIRED 18AWG FACTORY WIRED 12AWG Blower motor wiring chart Size Motor Sizes High Medium Low 02 12W Black Blue Red 03 12W Black Red Yellow 04 30W Black Blue Red 06 50W Black Red Yellow 08 50W...

Page 24: ...initial step is to visually inspect all of the equipment plenums connecting ductwork and piping Ensure that all systems are properly installed and supported and that all construction debris or foreign...

Page 25: ...in the closed position This will prevent any foreign material from entering the unit s heat exchanger and clogging valves and metering devices Strainers should be installed in the piping mains to prev...

Page 26: ...hese conditions persist recheck the system for air that may not have been properly vented during start up Proper water treatment is a specialized industry and therefore it is recommended to consult an...

Page 27: ...nal safety equipment when using spray paint Follow the manufacturer s directions for the products being used To repaint the factory powder coat finish prepare the surface by lightly sanding with 280 g...

Page 28: ...deviation from this could result in personnel injury or damage to the unit and will void the manufacturer s warranty All repair work should be done in such a way as to maintain the equipment in compl...

Page 29: ...lters tend to have less air pressure drop than throwaway filters Valves and piping No formal maintenance is required on the valve package components other than a visual inspection for possible leaks d...

Page 30: ...n Insulate all piping as required Ductwork connections n Install ductwork fittings and grilles as required n Flexible duct connections at unit n Proper supply and return grille type and size n Contro...

Page 31: ...29 SMART IDEAS Always the best climate for...

Page 32: ...ight prepaid If inspection shows the goods to be defective Zehnder will at its discretion repair or replace the said item s Defects arising from damage due to shipment improper installation negligence...

Page 33: ...document This warranty is extended only to the original purchaser from Zehnder Comfortable indoor ventilation Our comfortable indoor ventilation is energy efficient and provides a healthy indoor clima...

Page 34: ...hnder North America 100 Rittling Boulevard Buffalo NY 14220 USA T 844 934 6337 844 ZEHNDER sales zehnder rittling com www zehnder rittling com Zehnder March 2020 English subject to change without noti...

Reviews: