43 / 67
User’s Manual 3PH 100KTL-136KTL-HV
Rev. 1.0 24/02/2021
Identification: MD-AL-GI-00
Rev. 1.0 of 24/02/2021 - Application: GID
4)
Measure PV voltage of DC input with multimeter, verify DC input cable polar and connect DC connector
with inverter until hearing a slight sound indicated connection succeed.
Figure 36 - DC cable connection
Note: Please use multimeter to make sure the PV array positive pole and negative pole!
Dealing
:
If need to remove the PV connector from inverter side, please use the Removal Tool as below
diagram, move the connector gently.
Removal procedure
To remove the positive and negative connectors from the inverter, insert a removal tool in the bayonet
coupling and press the tool with adequate force, as shown in the figure below.
Before removing the positive and negative connectors, make sure that the
inverter’s circuit breaker is switched off. If not, the direct current may cause an
electric arc that could result in a fire
Warning