Vacc" function.
8) ADJUSTMENT
#04
This parameter determines the motor temperature level at which the “Motor
temperature” alarm is signalled. The range is from 70 °C to 160 °C with 10 °C
steps. This parameter must be adjusted only if the “Set temperature” (menu
“Set option”) parameter is programmed “Analog”.
9) ADJUSTMENT
#03
This parameter isn't used.
10) ADJUSTMENT #02
It adjusts the lower level of the battery discharge table.
11) ADJUSTMENT #01
It adjusts the upper level of the battery discharge table.
12) LOAD HM FROM MDI
For an explanation of this point see the MDI instrument handbook.
13) CHECK UP DONE
For an explanation of this point see the MDI instrument handbook.
14) CHECK UP TYPE
For an explanation of this point see the MDI instrument handbook.