BATTERY TYPE SETTING - via DIP switch 

 

 
Please check your battery manufacturer’s specifications to select the correct 

battery type. The unit provides for 4 battery types: Gel, AGM, WET (conventional 

lead acid), and LiFePO4. 

 

There is a DIP switch at the back of the solar charge controller, this Dip switch is 

used for presetting your battery type. Please refer to Figure 3.1 to make DIP 
switch setting for the proper battery chemical; the factory default setting is AGM 

battery type. 

 

Note: Once the Dip switch setting is finished, do not change the DIP switch 

unless disconnected from the battery; otherwise it may damage your battery. 

                                 

             

 

 
 

The unit has a 5-stage charging algorithm.

 

Soft Charge (Level 1) –  Bulk Charge (Level 2) –  Absorption charge (Level 3) –  

Equalizing Charge* (Level 4) - Float Mode (Level 5) 

 Figure 4.1

 

 

 

 

Soft Charge

 

When a battery suffers an over-discharge, the controller 

will softly ramp the battery voltage up to 10V. 

Bulk Charge

 

Maximum current charging until the battery rises to the 

Absorption level. 

Absorption Charge 

Constant voltage charge when the battery is over 85%. 

Equalization Charge*

  Only for WET battery, when the battery is deeply drained 

below 11.5V, it will automatically run this stage to bring 

the internal cells to an equal state to reduce any loss of 
capacity. 

Float Charge

 

Battery is fully charged and maintained at a safe level 

Voltage values are for 12V system, x 2 for 24V system 