Setting Operator Input Parameters,
Continued
Alarm to Relay Delay
Is a programmable time that can be entered to allow for
a period of time to occur between the initial issuance of
an alarm and the actual remote reporting of the alarm
via the alarm relay output.
1. 0 = No Relay Contact Delay
2. 1 - 240 = Number of Minutes Delay
3. > 240 = Disabled, No Alarm Relay Contact will
occur
To set the alarm delay time, figure 49,
press and
release the Select key. The Alarm to Delay value will
begin to flash when chosen. Use the Up Arrow key to
increase the value and the Down Arrow key to de-
crease the value. When a new value has been chosen,
press the Enter key to store the value.
Alarm to Call Out Delay
Is a programmable time that can be entered to allow for
a period of time to occur between the initial issuance of
an alarm and the actual automatic call out function via a
modem or Modbus communication port.
1. 0 = No Alarm Call Out Delay
2. 1 - 240 = Number of Minutes Delay
3. > 240 = Disabled, No Alarm Call Out will occur
To set the alarm to call out delay time, figure 50, press
and release the Select key. The Alarm to Callout
Delay value will begin to flash when chosen. Use the Up
Arrow key to increase the value and the Down Arrow
key to decrease the value. When a new value has been
chosen, press the Enter key to store the value.
MODBUS Address
In Modbus Protocol, each piece of equipment that will be
polled for information must be assigned a Slave I.D.
address, to allow the SCADA or other Host device to
properly address the device to be polled for information.
This parameter is to program the odorizer's Modbus
address. Any address from 1-247 may be programed.
If 0 is programed this function will be disabled, figure 51.
Note: the Modbus address is also used as the Sentry4 I.D.
pmp bat vmtr sig tnk
Maximum Time/Stroke
0 = Disabled
Select
Enter
Figure 49
pmp bat vmtr sig tnk
Alarm to Relay Delay
20 minutes
Select
Enter
Figure 50
pmp bat vmtr sig tnk
Alarm to Callout Dly
10 minutes
Select
Enter
Figure 51
pmp bat vmtr sig tnk
MODBUS Address
1 Device Address
Select
Enter