YZ Systems, Inc. • 3101 Pollok Drive • Conroe, Texas • USA • 77303 • P: 936.788.5593 • F: 936.788.5720
Page 110
NJEX 7300L ver.10012003
A
AA
A
A
PPENDIX
PPENDIX
PPENDIX
PPENDIX
PPENDIX
B:
B:
B:
B:
B: N-300 M
N-300 M
N-300 M
N-300 M
N-300 M
ODB
ODB
ODB
ODB
ODBUS
US
US
US
US
S
S
S
S
S
PECIFICA
PECIFICA
PECIFICA
PECIFICA
PECIFICATIONS
TIONS
TIONS
TIONS
TIONS
Integer Registers
The integer data type could be used for the Results data and configuration/control parameters. The
"holding registers" as referred to by the Modbus specification, are read/write registers. This 16-bit integer
data type can be manipulated using functions 3, 6, and 16.
Function 3, allows the host to read one or more holding registers per query.
Function 6, allows the host to write a single holding register per query.
Function 16, allows the host to write multiple holding registers per query.
Result Data Functions
The result data functions available via Modbus are listed below. The registers are accessed using Modbus
function 3.
Address
Access
Description
40001............ Read Only ............... HOU/LOU – Accum. Odorant Usage – High - Unsigned integer *See formatting info.
40002............ Read Only ............... HOU/LOU – Accum. Odorant Usage – Low - Unsigned integer *See formatting info.
40003 ........... Read Only ............... HOU/LOU - Accumulated Flow rate – High - Unsigned integer *See formatting info.
40004 ........... Read Only ............... HOU/LOU - Accumulated Flow rate – Low - Unsigned integer *See formatting info.
40005 .......... Read Only ............. HOU/LOU Start Date (Day of Month/Month) (1-31/1-12) - BCD
40006 .......... Read Only ............. HOU/LOU Start Date (Century/Year) (0000-9999) - BCD
40007 .......... Read Only ............. HOU/LOU Start Time (Seconds/Minutes) (00-59/00-59) - BCD
40008 .......... Read Only ............. HOU/LOU Start Time (Hours/Day of Week) (00-23/0-7) - BCD
40009 .......... Read Only ............. HOU/LOU End Date (Day of Month/Month) (1-31/1-12) - BCD
40010 .......... Read Only ............. HOU/LOU End Date (Century/Year) (0000-9999) – BCD
40011 ........... Read Only ............. HOU/LOU End Time (Seconds/Minutes) (00-59/00-59) – BCD
40012 .......... Read Only ............. HOU/LOU End Time (Hours/Day of Week) (00-23/0-7) – BCD
40013 .......... Read Only ............. Stroke Count High (0000-9999) – BCD
40014 .......... Read Only ............. Stroke Count Low (0000-9999) – BCD
40015 .......... Read Only ............. Total Odorant Injected High (0000-9999) – BCD *See formatting info.
40016 .......... Read Only ............. Total Odorant Injected Low (0000-9999) – BCD *See formatting info.
40017 .......... Read Only ............. Model Number – Unsigned Integer *See formatting info.
40018 .......... Read Only ............. Serial Number (xxxxx) – Unsigned Integer
40019 .......... Read Only ............. Verometer Calibration Data – Unsigned Integer *See formatting info.
40020 .......... Read Only ............. Odorant Tank Level (xxx %) – Unsigned Integer
40021 .......... Read Only ............. Expansion Tank Pressure (xxx.x psi / x.xxx bar) – Unsigned Integer
40022 .......... Read Only ............. Odorant Inlet Pressure (xxx.x psi / x.xxx bar) – Unsigned Integer
40023 .......... Read Only ............. Calculated Time per Stroke High – Unsigned Integer – sec.
40024 .......... Read Only ............. Calculated Time per Stroke Low – Unsigned Integer - (x.xx sec.)
40025 .......... Read Only ............. Verometer Level (xxx.x %) – Unsigned Integer
40026 .......... Read Only ............. Battery Voltage (xx.x volts) – Unsigned Integer