Appendix B: N-300 Modbus Specifications
* Model Specific Formatting information for Result Data functions
Address Description
40001
......................
High bytes for Accumulated odorant injected, combine with address 40002 for total.
40002
......................
6300GE/LE = .XXXXX, 7300GE/LE = X.XXXX, 8300GE/LE = XX.XXX (lbs),
6300GM/LM = .XXXXX, 7300GM/LM = X.XXXX, 8300GM/LM = XX.XXX (kg)
Note:
Low bytes only, combine with address 40001 for total odorant injected.
40003
......................
High bytes for Accumulated flow, combine with address 40004 for total.
40004
......................
6300GE = .XXXXX, 7300GE = X.XXXX, 8300GE = XX.XXX (MMCF/hr),
6300GM = X.XXX, 7300GM = XX.XXX, 8300GM = XXX.XX (M
3
/sec) 6300LE = XXX.XX,
7300LE = XXXX.X, 8300LE = XXXXX (gallons), 6300LM = XXX.XX, 7300LM = XXXX.X,
8300LM = XXXXX (liters), 6300/7300/8300LE (PPMV mode) = XXXXX (gallons),
6300/7300/8300LM (PPMV mode) = XXXXX (liters)
Note:
Low bytes only, combine with address 40003 for total accumulated flow.
40015
......................
High bytes only, combine with address 40016 for total odorant injected.
40016
......................
6300 = .XXXX, 7300 = X.XXX, 8300 = XX.XX (lbs/kg)
Note:
Low bytes only, combine with address 40015 for total odorant injected.
40017
......................
Model number format: 63XX = 6300, 73XX = 7300, 83XX = 8300. XX= 11= GE,
XX=12=GM, XX=21=LE, XX=22=LM. Example: 6311 = 6300 Gas English,
7322 = 7300 Liquid Metric
40019
......................
6300 = XX.XXX, 7300 = XXX.XX, 8300 = XXXX.X (cc)
Parameter functions
The result data functions available via Modbus are listed below. The registers are accessed using Modbus
functions 3, 6, and 16.
Note: The system must be stopped in order for any parameter changes to be accepted. An exception re-
sponse will be returned if a parameter change query is issued while the system is running. Once the param-
eter changes have been made, use coil 00009 to save the updated parameters before restarting the system.
Address Access
Description
40101
............
Read Only ............... Current Date (Day of Month / Month) (01-31 / 01-12) – BCD
40102
............
Read Only ............... Current Date (Century / Year) (0000-9999) – BCD
40103
............
Read Only ............... Current Time (Seconds / Minutes) (00-59 / 00-59) – BCD
40104
............
Read Only ............... Current Time (Hours / Day of Week) (00-23/01-07) – BCD
40105
............
Read/Write .............. Injection Rate - Unsigned Integer *See formatting info.
40106
............
Read/Write .............. Pump Displacement (cc/Stroke) – Unsigned Integer *See formatting info.
40107 ............ Read/Write .............. Odorant Density – Unsigned Integer X.XX (GE/LE = lbs/gal, GM/LM = g/cc)
40108
............
Read/Write .............. Proportional to Time Stroke Rate X.XX (minutes) – Unsigned Integer
40109
............
Read/Write .............. Maximum Gas Flow – Unsigned Integer *See formatting info.
40110 ............ Read/Write .............. Low Flow Shutoff (xx.x of Max Gas Flow) – Unsigned Integer
40111 ............ Read/Write .............. Flow No Signal (xx.x of Max Gas Flow) – Unsigned Integer
40112 ............ Read/Write .............. Maximum time per stroke (xxx minutes/stroke) – Unsigned Integer
40113 ............ Read/Write .............. Odorant Output (lbs/pulse) – Unsigned Integer *See formatting info.
40114 ............ Read/Write .............. Pulses per Second (xx Pulses/Seconds) – Unsigned Integer
40115 ............ Read/Write .............. Pulses per Minute / Pulses per Gallon (xx Pulses/Minute - Gas,
xx Pulses/Gal– Liquid PPMV) – Unsigned Integer