MINIMUM HEIGHT OF FLUE SYSTEM EXIT
NOTE : Dimensions are in millimetres
3000
or less
6
0
0
m
in
.
More than 3000
3000
.
Increase from
1000 min. until
clear within
3000 of flue top
L.
Conditions for Flues
(Fig. 4)
L1.
The FLUE shall extend to:
Not less than 600mm above the highest point on the roof if within 3.0m of that point,
or
Not less than 1000mm above the intersection point with the roof and not lower than any point of
the roof within 3.0m.
In any case the length of the flue shall not be less than 4.6m from the ash floor protector.
L2.
In some situations the Local Council may vary the above requirements.
L3.
The flue system must comply with AS/NZS2918:2001.
Fig. 4