Install-Xander_Insert_MASONRY - 2017-06-26.doc www.yunca.co.nz
Page 4 of 12
G.
Xander Wood Burner Dimensions
(Fig 1)
Blank fascia top panel (without vent) must be used for Masonry installations.
(The vented fascia top panel is for zero clearance installations only)
H.
Cavity Dimensions
H1.
Cavity should be prepared using the
following minimum clearances.
(Table 1) & (Fig. 2)
Increasing the
cavity dimensions slightly
will make installation easier.
Ensure wiring for fan
(Fig. 10)
is taken into
account when preparing cavity.
I.
Cavity Venting
I1.
A 10,000mm² vent must be installed at least
600mm from the base of the enclosure. This
can be any configuration as long as it
equates to at least 10,000mm².
[For example: 2 holes at 50 x 50mm or 1 hole at 100 x 100mm].
I2.
Similar vent(s) can also be added to the top of the masonry enclosure, however the
venting already provided via the flue cone and liner will be sufficient without this.
I3.
Suitable precautions should be taken to prevent rodents and/or debris from entering
or obscuring the air vents. If grilles are used; ensure the minimum vent area is
maintained through the grille.
Table 1
MASONRY CAVITY
MINIMUM DIMENSIONS (mm)
WIDTH
(W)
HEIGHT
(H)
DEPTH
(D)
680
600
530
Fig. 2
(Not to scale)
Fig. 1