Yudian AI-710JM Installation And Operation Manual Download Page 8

9. Advance Function

Alarm blocking at the beginning of power on

Sometimes the fault alarm may occur at the 

beginning of power on. In a heating system, at the 

beginning of power on, its temperature is much low-

er than the set point. If low limit and deviation low 

limit are set and the alarm conditions are satisfied, 

the instrument should alarm, but there is no prob-

lem in the system. Contrarily, in an refrigerating 

system, the unnecessary high limit or deviation high 

limit alarm may occur at the beginning of power 

on. Therefore, AI instruments offer the function of 

alarm blocking at the beginning of power on. When 

Act is set to rEbA or drbA, the corresponding low 

or high alarms are blocked until the alarm condition 

first clears. If the alarm condition is satisfied again, 

the alarm will work.

Communication function

S or S4 module can be installed at COMM slot to 

communicate with a computer. The instrument can 

be controlled by computer. AI instruments can be 

connected to the computer through RS232 or USB 

communication port. Every communication port of 

a computer can connect up to 60 AI instruments, 

or 80 AI instruments if a repeater is installed. A 

computer with 2 communication ports can connect 

up to 160 instruments. Please note that every instru-

ment connecting to the same communication line 

should be set to a unique communication address. 

If the number of instrument are enough, 2 or more 

computers can be used and a local network can be 

set up.

If users want to develop their own distributed 

control system by themselves, the communication 

protocol of AI instruments can be freely offered. 

There are many distributed control system software 

support AI instruments.

Fine control

Fine control means that the PID operating reso-

lution is ten times as high as the display resolu-

tion. For example, the temperature signal of the 

instrument displays 1°C, but the internal PID still 

operate and control as per 0.1°C resolution, thus can 

realize the control accuracy much higher than the 

display resolution. In former AI series instruments, 

only temperature signal adopts fine control mode. 

The new edition approves default fine control mode 

when the displayed value range is below 3,000 char-

acters (on most of industrial application occasions, 

the value should not exceed 3,000 characters) during 

linear input, so as to get higher control accuracy and 

more stable output. When the required display value 

range is larger than 3,000, AF.F=1.

User-defined input specifications

When INP is set to 64 larger than preset value, the 

input specification of the instrument switches to 

user-defined input. Set INP=22+64=86. The linear 

table can be edited, the setup method is as follows: 

set Loc parameter as 3698, and then enter the table 

setup status (if the original Loc=808, the Loc shall 

be zeroed, exit the parameter setting status, and then 

reenter the parameter setting status and set Loc as 

3698). Of which the parameter A 00 defines the use 

of the table, 0 is used to input non-linear measuring, 

1 is used to high temperature furnace non-linear 

control, with parameters of A01~A04 and d00~d60 

respectively set as follows:

A 00

=0 (fixed)

A 01

 defines input specfication

           Formula: 

A 01=A*1+E*16+G×*64

A is the range of measurement: 

A=0:  0~20mV (0-80Ω); 

A=1:  0~60mV (0-240Ω); 

A=2:  0~100mV (0-400Ω); 

A=3:  0~1V;

A=4:  0~5V, 

A=10, 0~20mA or 0~10V (MIO position installed with I4 or I31 

module)

E=0: Output value still should be determined as per ScH/ScL parame-

ters during linear input of signals. 

E=1: The table output value is the displayed value.

G is the type of sensor.

G=0: thermocouple; 

G=1: thermal resistance; 

G=2: linear voltage (current); 

G=3: linear resistance

For instance: Pt100 input; range 30~40

o

C;  every adjustment section 

at one degree

Long press Setup. Set

 inP

=86. Set 

dPt

=0.0.

LOC=3698 (Enter user-defined multi-section adjustment)

A00 = 0

A01 = 82 (Function setup. Set Pt100 configuration 82)

A02 = 300.0 (Initial temperature at 30

o

C)

A03 = 100.0

A04 = 10.0

d00 = 30.00  d01 = 31.00  d02 = 32.00

d03 = 33.00  d04 = 34.00  d05 = 35.00

d06 = 36.00  d07 = 37.00  d08 = 38.00

d09 = 39.00  d10 = 40.00

Set the deivation directly to the particular temperature. If it is show-

ing 37oC but it is found higher, set d07 a little bit lower than 37.00.

  

YUDIAN Automation Co., Limited

YUDIAN (H.K) Automation Co., Limited 

12/F, Chun Hoi Commercial Building, 688 Shanghai Street, 

Kowloon, Hong Kong

Tel: +852-27708785    [email protected]    

http://www.yudian.com.hk

Summary of Contents for AI-710JM

Page 1: ...cy 0 1 full scale FS 1 digit Input adustable digital filter Pt100 Sampling time 80ms Measurement Range 100 300 C Cold Junction Error 0 05 C for each 1 C variation Safety Detection of opening of probe Temperature Shift 35ppm C Regulating Method On Off adjustable hytersis Artificial Intelligent Regulating with auto tuning Main Output SSR Voltage output 12VDC 30mA used to drive solid state relay Acti...

Page 2: ...c 2 Lower display window Displays SV parameter value or alarm message 3 Setup key For accessing parameter table and conforming param eter modification 4 Cursor shifting or control operation 5 Value down key or switch between RUN HOLD 6 Value uo key or STOP These value down and up keys raise or lower the value of the displayed function The raising lowering speed is proportional to the time the key ...

Page 3: ...em Before activating the auto tuning set point value SV should be set at the commonly used value or mean value Set the SV to a maximum one if the heat isolation of a furnace is good SV value is not allowed to be changed during auto tuning The time required for this process may takes seconds to hours 3 Control Hysteresis CHYS affects the result of auto tuning too Generally the least the CHYS the hi...

Page 4: ...nE Loc 0 Example If fast access to high limit alarm high deviation alarm and auto tuning is needed set EP1 HIAL EP2 HdAL EP3 At EP4 EP8 nonE The default settings may vary due to minor firmware version update or order request Master password is stored in PASd By default PASd 808 There is no password reset feature If the password is lost only firmware reload in factory can reset the password loc def...

Page 5: ...an be assigned as absolute high limit and low limit alarms Details please refer to the description of parameter AF AHyS Alarm Hysteresis Also known as dead band or lag To avoid frequent alarm on off action caused by the fluctuation of PV Usage of AHYS is shown above 0 2000 units AdiS Alarm Display oFF Hide alarm messages in the lower display on Alternately display alarm message in the lower displa...

Page 6: ...turns off when PV SV CHYS output turns on 0 2000 inP Input Specification Code Select input specification Inut is fixed in this instrument with corresponding range of measurement 22 Pt100 100 300 00 C 22 dpt Display Resolution Four display formats 0 0 0 0 00 0 000 are selectable When inP 22 the internal resolution is 0 01 C Display format 0 0 or 0 00 are available 0 0 0 00 SCL Source Low Limit Defi...

Page 7: ...inear input is 3 200 units F 1 Wide range display mode which is selected when the required display value is larger than 3 200 G 0 When the sensor is broken PV value will increase and trigger the high limit alarm High limit alarm should be set below the input scale high limit G 1 When the sensor is broken PV value will increase and NOT trigger the high limit alarm Pleaes note that High Limit Alarm ...

Page 8: ... control mode The new edition approves default fine control mode when the displayed value range is below 3 000 char acters on most of industrial application occasions the value should not exceed 3 000 characters during linear input so as to get higher control accuracy and more stable output When the required display value range is larger than 3 000 AF F 1 User defined input specifications When INP...

Reviews: