Yudian AI-710JM Installation And Operation Manual Download Page 7

Parameter

Parameter Ttile

Description

Range of 

Setting

Addr

Communication 

address

In the same communication line, different instrument should be set to dif-

ferent address.

0~80

bAud

Baud rate

Define baud rate within 1200~19,200bit/s

0~19.2K

AF

Advanced 

function

AF is used to select advanced function. The value of AF is calculated as below: 

AF=A x 1 + B x 2 + C x 4 + D x 8 + E x 16 + F x 32 + G x 64 + H x 128

A=0*: HdAL and LdAL work as deviation high and low limit alarms;

A=1: HdAL and LdAL work as high and low limit alarms, and the instrument 

can have two groups of high and low limit alarms.

B=0: Alarm and control hysteresis work as unilateral hysteresis;

B=1: As bilateral hysteresis.

C=0: The light bar indicates the output value;

C=1: The light bar indicates the process value (for instruments with light bar 

only); 

D=0: The common password “808” can access full parameter table;

D=1: The password to access parameter table will be “PASd” value;

E=0: Normal application on HIAL and LoAL;

E=1: HIAL and LoAL changed to deviation high alarm and deviation low 

alarm;

F=0: Fine control mode. The internal control resolution is 10 times as much 

as that of display, but the maximum display value during linear input is 3,200 

units;

F=1: Wide range display mode which is selected when the required display 

value is larger than 3,200;

G=0: When the sensor is broken, PV value will increase and trigger the high 

limit alarm. (High limit alarm should be set below the input scale high limit.)

G=1, When the sensor is broken, PV value will increase and NOT trigger the 

high limit alarm. Pleaes note that High Limit Alarm will delay for 30 seconds 

when this feature is activated.

H=0, AIBUS communication

H=1, MODBUS compatible communication.

*AF=0 is recommended.

0~255

PASd

Password

When PASd=0~255 OR AF.D=0, setting Loc=808 will enter this complete 

parameter table.

When PASd=256~9999 AND AF.D=1, only Loc=PASd can access this com-

plete parameter table.

Pay attention to configure PASd. If the password is lost, there is no way to 

access  the parameter table again until it is sent to factory reset.

0~9999

SPL

Low Limit of SV

Minimum value that SV is allowed to be.

-999~+3000 

unit

SPH

Upper limit of SV

Maximum value that SV is allowed to be.

EP1

Customized Field 

Parameter

Field Parameters 1~8 can be configured for commonly used parameters with-

out entering lock password. Set 

nonE

 to hide the particular EP parameter.

H1AL

(Default)

EP2

LoAL

(Default)

EP3

HdAL

(Default)

EP4

LdAL

(Default)

EP5

nonE

(Default)

EP6

nonE

(Default)

EP7

nonE

(Default)

EP8

nonE

(Default)

SYSTEM

FIELD P

ARAMETER

COMMUNICA

TION

SET POINT

Summary of Contents for AI-710JM

Page 1: ...cy 0 1 full scale FS 1 digit Input adustable digital filter Pt100 Sampling time 80ms Measurement Range 100 300 C Cold Junction Error 0 05 C for each 1 C variation Safety Detection of opening of probe Temperature Shift 35ppm C Regulating Method On Off adjustable hytersis Artificial Intelligent Regulating with auto tuning Main Output SSR Voltage output 12VDC 30mA used to drive solid state relay Acti...

Page 2: ...c 2 Lower display window Displays SV parameter value or alarm message 3 Setup key For accessing parameter table and conforming param eter modification 4 Cursor shifting or control operation 5 Value down key or switch between RUN HOLD 6 Value uo key or STOP These value down and up keys raise or lower the value of the displayed function The raising lowering speed is proportional to the time the key ...

Page 3: ...em Before activating the auto tuning set point value SV should be set at the commonly used value or mean value Set the SV to a maximum one if the heat isolation of a furnace is good SV value is not allowed to be changed during auto tuning The time required for this process may takes seconds to hours 3 Control Hysteresis CHYS affects the result of auto tuning too Generally the least the CHYS the hi...

Page 4: ...nE Loc 0 Example If fast access to high limit alarm high deviation alarm and auto tuning is needed set EP1 HIAL EP2 HdAL EP3 At EP4 EP8 nonE The default settings may vary due to minor firmware version update or order request Master password is stored in PASd By default PASd 808 There is no password reset feature If the password is lost only firmware reload in factory can reset the password loc def...

Page 5: ...an be assigned as absolute high limit and low limit alarms Details please refer to the description of parameter AF AHyS Alarm Hysteresis Also known as dead band or lag To avoid frequent alarm on off action caused by the fluctuation of PV Usage of AHYS is shown above 0 2000 units AdiS Alarm Display oFF Hide alarm messages in the lower display on Alternately display alarm message in the lower displa...

Page 6: ...turns off when PV SV CHYS output turns on 0 2000 inP Input Specification Code Select input specification Inut is fixed in this instrument with corresponding range of measurement 22 Pt100 100 300 00 C 22 dpt Display Resolution Four display formats 0 0 0 0 00 0 000 are selectable When inP 22 the internal resolution is 0 01 C Display format 0 0 or 0 00 are available 0 0 0 00 SCL Source Low Limit Defi...

Page 7: ...inear input is 3 200 units F 1 Wide range display mode which is selected when the required display value is larger than 3 200 G 0 When the sensor is broken PV value will increase and trigger the high limit alarm High limit alarm should be set below the input scale high limit G 1 When the sensor is broken PV value will increase and NOT trigger the high limit alarm Pleaes note that High Limit Alarm ...

Page 8: ... control mode The new edition approves default fine control mode when the displayed value range is below 3 000 char acters on most of industrial application occasions the value should not exceed 3 000 characters during linear input so as to get higher control accuracy and more stable output When the required display value range is larger than 3 000 AF F 1 User defined input specifications When INP...

Reviews: