4. CONNECTIONS

The connections may be varied due to 

firmware upgrade or tailor-made order. 

Please follow the connection diagram 

attached to the instrument.

Signal input

Input from TC is connected to 9 (posi-

tive) and 10 (negative).

Control Output

Solid-state relay (SSR) output of 12VD-

C/30mA is connected to 7 (positive) 

and 6 (negative).  

Alarms

Alarm 1 (coded as AU1) is connected to 

3 (NO) and 5 (common).

Alarm 2 (coded as AU2) is connected to   

4 (NO) and 5 (common). 

 

3. DESCRIPTION OF FACEPLATE

 1  Upper display window:  

     Displays PV, parameter code, etc.

 2  Lower display window: 

     Displays SV, parameter value, or alarm message

 3  Setup key: 

      For accessing parameter table and conforming param-

eter modification.

 4  Cursor shifting (or control operation)

 5  Value down key 

     (or switch between RUN/HOLD) 

 6  Value uo key (or STOP)

     These value down and up keys raise or lower the value 

of the displayed function. The raising (lowering) speed is 

proportional to the time the key is pushed. The procedure 

is not cyclical. When the maximum (minimum) of the 

setting range is reached with the key pushed, the raise 

(lower) function stops.

 7  Six LED indicating lights:

     MAN – Not used

     PRG – Control is in action

     COM - Communiction with host device in action

     OP1 - Main output in action 

     AU1 - Alarm at AU1 on

     AU2 - Alarm at AU2 on

 

 

AI-3502M/3504M/3506M 

人工智能温度控制器/工业调节器 

产品说明书 

 

 

Summary of Contents for AI-710JM

Page 1: ...cy 0 1 full scale FS 1 digit Input adustable digital filter Pt100 Sampling time 80ms Measurement Range 100 300 C Cold Junction Error 0 05 C for each 1 C variation Safety Detection of opening of probe Temperature Shift 35ppm C Regulating Method On Off adjustable hytersis Artificial Intelligent Regulating with auto tuning Main Output SSR Voltage output 12VDC 30mA used to drive solid state relay Acti...

Page 2: ...c 2 Lower display window Displays SV parameter value or alarm message 3 Setup key For accessing parameter table and conforming param eter modification 4 Cursor shifting or control operation 5 Value down key or switch between RUN HOLD 6 Value uo key or STOP These value down and up keys raise or lower the value of the displayed function The raising lowering speed is proportional to the time the key ...

Page 3: ...em Before activating the auto tuning set point value SV should be set at the commonly used value or mean value Set the SV to a maximum one if the heat isolation of a furnace is good SV value is not allowed to be changed during auto tuning The time required for this process may takes seconds to hours 3 Control Hysteresis CHYS affects the result of auto tuning too Generally the least the CHYS the hi...

Page 4: ...nE Loc 0 Example If fast access to high limit alarm high deviation alarm and auto tuning is needed set EP1 HIAL EP2 HdAL EP3 At EP4 EP8 nonE The default settings may vary due to minor firmware version update or order request Master password is stored in PASd By default PASd 808 There is no password reset feature If the password is lost only firmware reload in factory can reset the password loc def...

Page 5: ...an be assigned as absolute high limit and low limit alarms Details please refer to the description of parameter AF AHyS Alarm Hysteresis Also known as dead band or lag To avoid frequent alarm on off action caused by the fluctuation of PV Usage of AHYS is shown above 0 2000 units AdiS Alarm Display oFF Hide alarm messages in the lower display on Alternately display alarm message in the lower displa...

Page 6: ...turns off when PV SV CHYS output turns on 0 2000 inP Input Specification Code Select input specification Inut is fixed in this instrument with corresponding range of measurement 22 Pt100 100 300 00 C 22 dpt Display Resolution Four display formats 0 0 0 0 00 0 000 are selectable When inP 22 the internal resolution is 0 01 C Display format 0 0 or 0 00 are available 0 0 0 00 SCL Source Low Limit Defi...

Page 7: ...inear input is 3 200 units F 1 Wide range display mode which is selected when the required display value is larger than 3 200 G 0 When the sensor is broken PV value will increase and trigger the high limit alarm High limit alarm should be set below the input scale high limit G 1 When the sensor is broken PV value will increase and NOT trigger the high limit alarm Pleaes note that High Limit Alarm ...

Page 8: ... control mode The new edition approves default fine control mode when the displayed value range is below 3 000 char acters on most of industrial application occasions the value should not exceed 3 000 characters during linear input so as to get higher control accuracy and more stable output When the required display value range is larger than 3 000 AF F 1 User defined input specifications When INP...

Reviews: