Yudian AI-710JM Installation And Operation Manual Download Page 3

6. OPERATION

Parameter Setting

At the basic display, press      and hold for about 2 

seconds to access 

Field Parameter Table

. Press 

to proceed to next parameter. Press      ,      or        to 

modify values. Press      to decrease the value.  

Press       to increase the value. There is a dot flashing 

while the value is changing just like a cursor. Hold 

the keys will speed up the value changing speed, as 

well as the flashing frequency of the cursor.  

Press     to move the designated digit position.  

Press      to save and proceed to the next parameter. 

Hold       to scroll down the parameter table quickly. 

Press and hold       more than 2 seconds goes back 

to the previous parameter. Press and hold       (don’t 

release) plus      simultaneously escape parameter 

setting back to 

Basic Display

. The instrument will 

automatically escape to 

Basic Display 

if no key is 

pressed for 25 seconds but any change made to the 

last parameter will not be saved.

Short-cut Keys

Certain frequently used operations can be done by 

short-cut keys. Those keys can be disabled.

Changing SV: 

Press       ,       or       to change.

Auto-tuning (AT):

 Press       and hold for about 2 sec-

onds until  “At” shows up. Press     to toggle “oFF” to 

“on” in the lower display. Press     to start auto-tun-

ing. The lower display will flash “At”. After two 

oscillating cycles in “ON-OFF” control mode, PID 

parameters will be calculated. To quit auto-turn-

ing, perform the same operation by pressing      for 

2 seconds. Change “on” to “oFF” and press     to 

confirm to quit. 

Note

 

1. Advanced artificial intelligent technology and PID regulating algo-

rithm by AI-710JM, which is named as “APID” is able to overcome the 

overshoot issue by standard PID algorithm.

2. PID values vary from different system. Before activating the 

auto-tuning, set point value, SV, should be set at the commonly 

used value or mean value. Set the SV to a maximum one if the heat 

isolation of a furnace is good. SV value is not allowed to be changed 

during auto-tuning. The time required for this process may takes 

seconds to hours.

3. Control Hysteresis, CHYS, affects the result of auto-tuning too. 

Generally the least the CHYS, the higher is the PID auto-tuning accu-

racy. However low CHYS value may cause incorrect ON-OFF output 

during fluctuating input. CHYS=2.0 is recommended.

4. The PID values may not give the best performance immediately 

after the auto-tuning is finished. The performance will gradually 

improve over some time because there is a learning feature.

5. Regardless of auto-tuning or manual tuning, the control period, Ctl, 

will be limited not longer than 3 seconds, no matter what value it is 

set previously, to increase the accuracy and to provide better response 

time (manual tuning).

5. DISPLAY

Basic Display

When the instrument is powered, the upper display 

and lower display show the model number and firm-

ware version respectively. After around 3 seconds, 

the displays show the process value (PV) and set 

value (SV) respectively. This basic display remains 

until there is a key pressed.

 

System Message

Following warning or status message may show up.

Symbol

Description

orAL

Out-of-range alarm due to incorrent 

input specification / Input wires 

disconnected / Broken thermocouple 

/ Short-circuited input 

#

HIAL

High limit alarm* 

LoAL

Low limit alarm*

HdAL

Deviation high alarm*

LdAL

Deviation low alarm*

EErr

Internal data lost. Factory repair 

required.

StoP

The instrument is in STOP status. No 

output is given out.

* The alarm messages can be turned off by setting parameter AdIS to 

oFF. 

# When orAL appeared, the instrument will cut off the output after 
a while.

Summary of Contents for AI-710JM

Page 1: ...cy 0 1 full scale FS 1 digit Input adustable digital filter Pt100 Sampling time 80ms Measurement Range 100 300 C Cold Junction Error 0 05 C for each 1 C variation Safety Detection of opening of probe Temperature Shift 35ppm C Regulating Method On Off adjustable hytersis Artificial Intelligent Regulating with auto tuning Main Output SSR Voltage output 12VDC 30mA used to drive solid state relay Acti...

Page 2: ...c 2 Lower display window Displays SV parameter value or alarm message 3 Setup key For accessing parameter table and conforming param eter modification 4 Cursor shifting or control operation 5 Value down key or switch between RUN HOLD 6 Value uo key or STOP These value down and up keys raise or lower the value of the displayed function The raising lowering speed is proportional to the time the key ...

Page 3: ...em Before activating the auto tuning set point value SV should be set at the commonly used value or mean value Set the SV to a maximum one if the heat isolation of a furnace is good SV value is not allowed to be changed during auto tuning The time required for this process may takes seconds to hours 3 Control Hysteresis CHYS affects the result of auto tuning too Generally the least the CHYS the hi...

Page 4: ...nE Loc 0 Example If fast access to high limit alarm high deviation alarm and auto tuning is needed set EP1 HIAL EP2 HdAL EP3 At EP4 EP8 nonE The default settings may vary due to minor firmware version update or order request Master password is stored in PASd By default PASd 808 There is no password reset feature If the password is lost only firmware reload in factory can reset the password loc def...

Page 5: ...an be assigned as absolute high limit and low limit alarms Details please refer to the description of parameter AF AHyS Alarm Hysteresis Also known as dead band or lag To avoid frequent alarm on off action caused by the fluctuation of PV Usage of AHYS is shown above 0 2000 units AdiS Alarm Display oFF Hide alarm messages in the lower display on Alternately display alarm message in the lower displa...

Page 6: ...turns off when PV SV CHYS output turns on 0 2000 inP Input Specification Code Select input specification Inut is fixed in this instrument with corresponding range of measurement 22 Pt100 100 300 00 C 22 dpt Display Resolution Four display formats 0 0 0 0 00 0 000 are selectable When inP 22 the internal resolution is 0 01 C Display format 0 0 or 0 00 are available 0 0 0 00 SCL Source Low Limit Defi...

Page 7: ...inear input is 3 200 units F 1 Wide range display mode which is selected when the required display value is larger than 3 200 G 0 When the sensor is broken PV value will increase and trigger the high limit alarm High limit alarm should be set below the input scale high limit G 1 When the sensor is broken PV value will increase and NOT trigger the high limit alarm Pleaes note that High Limit Alarm ...

Page 8: ... control mode The new edition approves default fine control mode when the displayed value range is below 3 000 char acters on most of industrial application occasions the value should not exceed 3 000 characters during linear input so as to get higher control accuracy and more stable output When the required display value range is larger than 3 000 AF F 1 User defined input specifications When INP...