Yudian AI-710JM Installation And Operation Manual Download Page 5

8. PARAMETER SETTING (Continued)

Complete Parameters Table

The parameters is listed under 8 groups which is alarm, control, input, output, communication, system, set 

point and Field Parameters. 

Parameter

Parameter Ttile

Description

Range of 

Setting

HiAL

High Limit Alarm

Alarm turns on when PV>HIAL

Alarm turns off when PV<HIAL-AHYS,

Set to the maximum value to disable the alarm.

Alarm output location can be defined by parameter AOP. All alarms can be 

assigned to AL1, AL2, AU1, AU2 or none. More alarm allocation is explained 

in AOP section below.

-9990~ 

+32000 units

LoAL

Low Limit Alarm

Alarm turns on when PV<LoAL

Alarm turns off when PV>LoAL+AHYS

Set to the minimum value to disable the alarm.

HIAL and LoAL can be assigned as deviation alarms. Details please refer to 

the description of parameter AF.

HdAL

Deviation High 

Alarm

Alarm turns on when PV-SV>HdAL;

Alarm turns off when PV-SV<HdAL-AHYS

Set to the maximum value to disable the alarm.

LdAL

Deviation Low 

Alarm

Alarm turns on when PV-SV<LdAL

Alarm turns off when PV-SV>LdAL+AHYS

Set to the minimum value to disable the alarm.

HdAL and LdAL can be assigned as absolute high limit and low limit alarms. 

Details please refer to the description of parameter AF.

AHyS

Alarm Hysteresis

Also known as dead band or lag. To avoid frequent alarm on-off action caused 

by the fluctuation of PV. Usage of AHYS is shown above.

0~2000 units

AdiS

Alarm Display

oFF

: Hide alarm messages in the lower display 

on

: Alternately display alarm message in the lower display [Recommended]

oFF

 / 

on

AOP

Alarm Output 

Position

Assign alarm (HdAL/LdAL/LoAL/HiAL) to different module slot position 

(AL1/AL2/AU1/AU2)

AOP Code

HdAL

LdAL

LoAL

HiAL

0

: Disabled

1

: AL1 (ALM slot)

N/A

N/A

N/A

N/A

2

: AL2 (ALM slot)

N/A

N/A

N/A

N/A

3

: AU1 (AUX slot)

4

: AU2 (AUX slot)*

 

Example:  

AOP

=

3303

HdAL and LdAL are sent to AU1. LoAL is disabled. HiAL is sent to AU1.

L3 dual relay output module must be install in AUX slot to use AU2.

0~6666

CtrL

Control Mode

onoF

: on-off control, for situation not requiring high precision

APid

: advanced artificial intelligence PID control. (Recommended)

nPId

: standard PID algorithm with anti integral-saturation function (no in-

tegral when PV-SV > proportional band)

onoF

/

APid

nPid

Srun

Running Status

run

: Control is in effect. “PRG” indicator lights up.

StoP

: Control is stopped. Lower display keeps flashing 

StoP

. “PRG” indi-

cator goes off.

HoLd

: Control is paused. 

StoP

 / 

run

 / 

HoLd

ALARM

Summary of Contents for AI-710JM

Page 1: ...cy 0 1 full scale FS 1 digit Input adustable digital filter Pt100 Sampling time 80ms Measurement Range 100 300 C Cold Junction Error 0 05 C for each 1 C variation Safety Detection of opening of probe Temperature Shift 35ppm C Regulating Method On Off adjustable hytersis Artificial Intelligent Regulating with auto tuning Main Output SSR Voltage output 12VDC 30mA used to drive solid state relay Acti...

Page 2: ...c 2 Lower display window Displays SV parameter value or alarm message 3 Setup key For accessing parameter table and conforming param eter modification 4 Cursor shifting or control operation 5 Value down key or switch between RUN HOLD 6 Value uo key or STOP These value down and up keys raise or lower the value of the displayed function The raising lowering speed is proportional to the time the key ...

Page 3: ...em Before activating the auto tuning set point value SV should be set at the commonly used value or mean value Set the SV to a maximum one if the heat isolation of a furnace is good SV value is not allowed to be changed during auto tuning The time required for this process may takes seconds to hours 3 Control Hysteresis CHYS affects the result of auto tuning too Generally the least the CHYS the hi...

Page 4: ...nE Loc 0 Example If fast access to high limit alarm high deviation alarm and auto tuning is needed set EP1 HIAL EP2 HdAL EP3 At EP4 EP8 nonE The default settings may vary due to minor firmware version update or order request Master password is stored in PASd By default PASd 808 There is no password reset feature If the password is lost only firmware reload in factory can reset the password loc def...

Page 5: ...an be assigned as absolute high limit and low limit alarms Details please refer to the description of parameter AF AHyS Alarm Hysteresis Also known as dead band or lag To avoid frequent alarm on off action caused by the fluctuation of PV Usage of AHYS is shown above 0 2000 units AdiS Alarm Display oFF Hide alarm messages in the lower display on Alternately display alarm message in the lower displa...

Page 6: ...turns off when PV SV CHYS output turns on 0 2000 inP Input Specification Code Select input specification Inut is fixed in this instrument with corresponding range of measurement 22 Pt100 100 300 00 C 22 dpt Display Resolution Four display formats 0 0 0 0 00 0 000 are selectable When inP 22 the internal resolution is 0 01 C Display format 0 0 or 0 00 are available 0 0 0 00 SCL Source Low Limit Defi...

Page 7: ...inear input is 3 200 units F 1 Wide range display mode which is selected when the required display value is larger than 3 200 G 0 When the sensor is broken PV value will increase and trigger the high limit alarm High limit alarm should be set below the input scale high limit G 1 When the sensor is broken PV value will increase and NOT trigger the high limit alarm Pleaes note that High Limit Alarm ...

Page 8: ... control mode The new edition approves default fine control mode when the displayed value range is below 3 000 char acters on most of industrial application occasions the value should not exceed 3 000 characters during linear input so as to get higher control accuracy and more stable output When the required display value range is larger than 3 000 AF F 1 User defined input specifications When INP...