III. FRONT PANEL AND OPERATION 

 

Process Value(PV), or parameter code

 

 

Set Value(SV), alarming code, or value of a parameter

 

 

Setup key, accessing parameter table, and confirming change.

 

 

Data shift key, also for activating auto turning 

 

 

Data decrease key

 

 

Data increase key

 

 

Status display LED, 

 

OP1 – Output 
AU1 – Alarm 1 
AU2 – Alarm 2 
RUN – Controlling process running

 

 

Default display status:   

When power is on, the process value (PV) and the set value (SV) are shown. lf the input signal is out of the measurable range (for example, 
the thermocouple or RTD circuit is break or input specification is not correctly set), the upper display will blink “orA” and high limit or low 
limit of specified input. The instrument will automatically stop the output. 

 

IV. OPERATION DESCRIPTION 

 

Set Value Setting: 

During default display status, if the parameter lock “Loc” isn't locked, user can set setpoint (SV) by pressing 

Y

 

V

 

U

 keys. Press 

V

 

key to decrease the value, 

U

 key to increase the value, and 

Y

 key to move to the dot to the desiired digit (acting as a pointer). Keep 

pressing 

V

 or 

U

 will speed up value change. The range of setpoint is limited by parameter SPH with default range 0 to 400.   

 

 

Parameter Setting:

 

During default display status, press and hold 

3

 for 2 seconds will access Field Parameter Table (See 

V. PARAMETER AND 

SETTING

). Press 

3

 to proceed to the next parameter. If parameter table have not been locked, press 

Y

 

V

 

U

 will change the 

parameter. Press and hold 

Y

 for 2 second returns to the preceding parameter. Press 

Y

 (don't release) and then press  

3

 

simultaneously jumps out from parameter setting to the default status. The instrument will also jumps out auomatically from the 
parameter table if no key is pressed in 30 seconds. Setting Loc=808 and then press 

3

 will access System Parameter Table (See 

V. 

PARAMETER AND SETTING

 

 

AI artificial intelligence control and auto tuning 

When AI artificial intelligence control algorithm is selected (CrL=AI), the P,I, and D parameters can be calculated automatically by 
auto-tuning. In default display status, press and hold 

Y

 for 2 seconds, “At” auto-tuning parameter will show. Press 

U

 to change the 

value of “At” from “oFF” to “on”, then press 

3

 to activate the auto-tuning. During auto-tuning, the instrument runs on-off control for two 

cycles. The instrument will calculate the optimal P, I and D control parameter values and returns to default display. If user want to 
interrupt the auto tuning process, press and hold the 

Y

 for 2 seconds. Change “At” from “on” to “oFF” and press 

3

 to confirm. The   

auto-tuning process will be cancelled and new P, I and D values will be calculated. 
 

Note 1: 

The P, I and D parameters obtained from auto-tuning are dependent to the set value. It is recommended to set a set value to an 
often-used value or mean value to perform auto-tuning. For the ovens with good heat preservation, the set value can be set at 
the highest applicable temperature. Depending on hardware setup, the auto-tuning may take from a few seconds to a few hours. 

 

Note 2:

 

Parameter Ctl (on-off differential, control hysteresis) has influence on the accuracy of auto-tuning.    Generally, the smaller the 
value of Ctl, the higher the precision of auto tuning.    But Ctl parameter value should be large enough to prevent the instrument 
from error action around set value due to the oscillation of input. Ctl is recommended to be 2.0. 

 

Note 3: 

Self-learning function enables the instrument to control better and better after time.   

Summary of Contents for AI-208

Page 1: ...omation Technology Co Ltd Website http www yudian us http www yudian com hk Email sales yudian com hk Tel 852 2770 8785 Fax 852 2770 8796 ARTIFICIAL INTELLIGENCE TEMPERATURE CONTROLLER AI 208 V7 8 Ope...

Page 2: ...tiple thermocouples and RTDs are selectable Suitable for 0 999 application Maximum support two alarms contact output Universal supply power 100 240VAC 2 Part 2 Front panel dimension Panel Size Front P...

Page 3: ...city 2A 250VAC normal open support AU1 and AU2 alarm output G SSR voltage output module 30mA 5VDC D1 sized controller is fixed to SSR output G and no module option provided i e AI 208 D1 G AI 208 D1 G...

Page 4: ...ously jumps out from parameter setting to the default status The instrument will also jumps out auomatically from the parameter table if no key is pressed in 30 seconds Setting Loc 808 and then press...

Page 5: ...ction because of the fluctuation of PV AHY 2 by default 0 200 AOP Alarm output assignment HdA x100 LdA LoA x10 HIA x1 0 0 0 1 AU1 1 AU1 1 AU1 2 AU2 2 AU2 2 AU2 5 AU1 AU1 6 AU2 AU1 7 AU1 8 AU2 9 AU1 AU...

Page 6: ...s 0 200 InP Input specification Thermocouples RTD 0 K 4 E 5 J 7 N 21 Pt100 0 21 dPt Resolution 0 or 0 0 selectable 0 0 is valid for 0 99 9 display Scb Input shift Scb is used to make input shift to co...

Page 7: ...ed is for upright panel dimension A A1 E E1 For panel dimension B B1 F F1 please rotate the diagram clockwise by 90 degree Panel dimension D 72 x 72mm Panel dimension D1 D2 48 x 48mm Remarks 1 Thermoc...

Reviews: