VI.
INSTRUMENT INSTALLATION AND WIRING DIAGRAM
Panel dimension A1, B1, E1 or F1
Panel dimension A, B, E or F
Main Output
Alarm Output
Main Output
Alarm Output
The diagram illustrated is for upright panel dimension A/A1/E/E1.
For panel dimension B/B1/F/F1, please rotate the diagram clockwise by 90 degree
.
Panel dimension D (72 x 72mm)
Panel dimension D1/D2 (48 x 48mm)
Remarks
1. Thermocouples compensate wires should be directly screwed to the back of the instrument. No extension by normal
conducting wire should be used. Please pay attention to the polarity of the compensate wires.
2. The solid-state relay (SSR) externally connected should provide 2300 V isolation between input/output-to-power line.
(CE requirement)