V. PARAMETER AND SETTING
Parameter
Title
Description
Range
Field Parameter Table (Press and hold
3
for 2 seconds to access)
HIA
High limit alarm
Alarm on when PV (Process Value) >HIA;
alarm off when PV<HIA-AHY
0
~
999
℃
LoA
Lower limit alarm Alarm on when PV (Process Value) < LoA;
alarm off when PV > LoA+AHY
0
~
999
℃
HdA
Deviation high
alarm
Alarm on when PV-SV>HdA;
alarm off when PV-SV<HdA-AHY
0
~
999
℃
LdA
Deviation low
alarm
Alarm on when PV-SV<LdA;
alarm off when PV-SV>LdA+AHY
0
~
999
℃
Loc Parameter
lock
Loc=0: Allowed to change HIA, LoA, HdA, LdA and SV.
Loc=1: Allowed to read only HIA, LoA, HdA, LdA but to change SV.
Loc=2~3: Allowed to change HIA, LoA, HdA. LdA but read only SV.
Loc=4~255: NOT allowed to change any parameters nor SV.
Loc=808, Set to 808 and press
3
to unlock the System Parameter Table
.
0
~
255
System Parameter Table (Loc=808 to unlock)
AHY
Alarm Hysteresis Avoid frequent alarm on-off action because of the fluctuation of PV
AHY=2 by default.
0~200
AOP
Alarm output
assignment
HdA &
(x100)
LdA
LoA
(x10)
HIA
(x1)
0
±
±
0
±
0
±
1
AU1
±
1
AU1
1
AU1
2
AU2
±
2
AU2
2
AU2
5
AU1
AU1
6
AU2 AU1
7
±
AU1
8
±
AU2
9
AU1
AU2
Example: AOP=901 refers to HdA assigned to AU1, LdA to AU2,
without LoA and HIA to AU1.
0~922
CrL Control
mode
z
onF : ON-OFF control. When PV>SV, output stops and heating
stops. When PV<SV-AHY, output resumes.
z
AI : AI-PID control. The output time proportion can adjusted by
parameter Ctl
Act Acting
method
rE: Reverse acting. Increase in measured variable causes a decrease
in the output, such as heating control.
dr: Direct acting. Increase in measured variable causes an increase in
the output, such as refrigerating control.
rEb: Reverse acting with low limit alarm and deviation low alarm
blocking at the beginning of power on.
drb: Direct acting with high limit alarm and deviation high alarm
blocking at the beginning of power on.
rE , dr ,
rEb, drb
P Proportion
band
Proportion band in PID with unit
℃
or
℉
but not the percentage of the
input scale.
1~999
I
Time of integral
Time of integral in PID. No integral effect when I=0
0~999 sec
d
Time of
derivative
Time of derivative in PID with unit 0.1 second. No derivative effect
when d=0
0~999 sec