V. PARAMETER AND SETTING

 

 

 

Parameter

 Title 

Description 

Range 

Field Parameter Table (Press and hold 

3

 

for 2 seconds to access) 

HIA 

High limit alarm 

Alarm on when PV (Process Value) >HIA; 

alarm off when PV<HIA-AHY 

0

999

 

LoA 

Lower limit alarm  Alarm on when PV (Process Value) < LoA; 

alarm off when PV > LoA+AHY 

0

999

 

HdA 

Deviation high 

alarm 

Alarm on when PV-SV>HdA;   
alarm off when PV-SV<HdA-AHY 

0

999

 

LdA 

Deviation low 

alarm 

Alarm on when PV-SV<LdA;   
alarm off when PV-SV>LdA+AHY 

0

999

 

Loc Parameter 

lock 

Loc=0: Allowed to change HIA, LoA, HdA, LdA and SV. 

Loc=1: Allowed to read only HIA, LoA, HdA, LdA but to change SV. 

Loc=2~3: Allowed to change HIA, LoA, HdA. LdA but read only SV. 

Loc=4~255: NOT allowed to change any parameters nor SV. 

Loc=808, Set to 808 and press 

3

 to unlock the System Parameter Table

0

255 

System Parameter Table (Loc=808 to unlock)

 

AHY 

Alarm Hysteresis  Avoid frequent alarm on-off action because of the fluctuation of PV 

AHY=2 by default. 

0~200 

AOP 

Alarm output 

assignment 

HdA &

 (x100)

LdA 

 

 LoA 

(x10) 

 HIA 

(x1) 

±

 

±

 

0

±

 

0

±

 

AU1 

±

 

1

AU1 

1

AU1 

AU2 

±

 

2

AU2 

2

AU2 

AU1 

AU1

AU2 AU1 

 

 

 

 

±

 

AU1

±

 

AU2

AU1 

AU2

Example: AOP=901 refers to HdA assigned to AU1, LdA to AU2, 

without LoA and HIA to AU1. 

0~922 

CrL Control 

mode 

z

 

onF : ON-OFF control. When PV>SV, output stops and heating 
stops. When PV<SV-AHY, output resumes. 

z

 

AI : AI-PID control. The output time proportion can adjusted by 
parameter Ctl 

 

Act Acting 

method 

rE: Reverse acting. Increase in measured variable causes a decrease 

in the output, such as heating control. 

dr: Direct acting. Increase in measured variable causes an increase in 

the output, such as refrigerating control. 

rEb: Reverse acting with low limit alarm and deviation low alarm 

blocking at the beginning of power on. 

drb: Direct acting with high limit alarm and deviation high alarm 
blocking at the beginning of power on. 

rE , dr ,   

rEb, drb 

P Proportion 

band 

Proportion band in PID with unit 

or 

  but not the percentage of the 

input scale. 

1~999 

Time of integral 

Time of integral in PID. No integral effect when I=0 

0~999 sec 

Time of 

derivative 

Time of derivative in PID with unit 0.1 second. No derivative effect 

when d=0 

0~999 sec 

Summary of Contents for AI-208

Page 1: ...omation Technology Co Ltd Website http www yudian us http www yudian com hk Email sales yudian com hk Tel 852 2770 8785 Fax 852 2770 8796 ARTIFICIAL INTELLIGENCE TEMPERATURE CONTROLLER AI 208 V7 8 Ope...

Page 2: ...tiple thermocouples and RTDs are selectable Suitable for 0 999 application Maximum support two alarms contact output Universal supply power 100 240VAC 2 Part 2 Front panel dimension Panel Size Front P...

Page 3: ...city 2A 250VAC normal open support AU1 and AU2 alarm output G SSR voltage output module 30mA 5VDC D1 sized controller is fixed to SSR output G and no module option provided i e AI 208 D1 G AI 208 D1 G...

Page 4: ...ously jumps out from parameter setting to the default status The instrument will also jumps out auomatically from the parameter table if no key is pressed in 30 seconds Setting Loc 808 and then press...

Page 5: ...ction because of the fluctuation of PV AHY 2 by default 0 200 AOP Alarm output assignment HdA x100 LdA LoA x10 HIA x1 0 0 0 1 AU1 1 AU1 1 AU1 2 AU2 2 AU2 2 AU2 5 AU1 AU1 6 AU2 AU1 7 AU1 8 AU2 9 AU1 AU...

Page 6: ...s 0 200 InP Input specification Thermocouples RTD 0 K 4 E 5 J 7 N 21 Pt100 0 21 dPt Resolution 0 or 0 0 selectable 0 0 is valid for 0 99 9 display Scb Input shift Scb is used to make input shift to co...

Page 7: ...ed is for upright panel dimension A A1 E E1 For panel dimension B B1 F F1 please rotate the diagram clockwise by 90 degree Panel dimension D 72 x 72mm Panel dimension D1 D2 48 x 48mm Remarks 1 Thermoc...

Reviews: