524581-YIM-I-0512
Johnson Controls Unitary Products
43
ZJ120 (10 Ton) Side Duct
Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive
Standard 2 HP & Drive
Hi Static 3 HP & Drive
2600
675
0.53
726
0.74
776
0.94
824
1.12
870
1.30
914
1.48
957
1.65
1000
1.82
1041
1.99
1082
2.17
2800
686
0.63
738
0.84
787
1.04
835
1.23
881
1.41
925
1.58
969
1.76
1011
1.93
1052
2.10
1093
2.27
3000
699
0.75
750
0.96
800
1.16
847
1.34
893
1.52
938
1.70
981
1.87
1024
2.04
1065
2.21
1106
2.39
3200
713
0.88
764
1.09
814
1.28
861
1.47
907
1.65
952
1.83
995
2.00
1037
2.17
1079
2.34
1119
2.52
3400
728
1.02
779
1.23
829
1.43
877
1.61
923
1.79
967
1.97
1010
2.14
1053
2.31
1094
2.48
1135
2.66
3600
745
1.18
796
1.39
846
1.59
893
1.77
939
1.95
984
2.13
1027
2.30
1069
2.47
1111
2.64
1152
2.82
3800
763
1.36
815
1.57
864
1.76
912
1.95
958
2.13
1002
2.31
1046
2.48
1088
2.65
1129
2.82
1170
3.00
4000
783
1.55
835
1.76
884
1.96
932
2.15
978
2.33
1022
2.50
1066
2.67
1108
2.84
1149
3.02
1190
3.19
4200
805
1.77
856
1.98
906
2.17
953
2.36
999
2.54
1044
2.72
1087
2.89
1129
3.06
1171
3.23
1211
3.41
4400
828
2.00
879
2.21
929
2.41
976
2.59
1022
2.77
1067
2.95
1110
3.12
1152
3.29
-
-
-
-
4600
852
2.25
904
2.46
953
2.66
1001
2.85
1047
3.03
1092
3.20
1135
3.37
-
-
-
-
-
-
4800
879
2.52
930
2.73
980
2.93
1027
3.12
1073
3.30
-
-
-
-
-
-
-
-
-
-
5000
906
2.81
958
3.02
1007
3.22
1055
3.41
-
-
-
-
-
-
-
-
-
-
-
-
3 HP & Field Supplied Drive
ZJ150 (12.5 Ton) Side Duct
Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive
Standard 3 HP & Drive
3200
713
0.88
764
1.09
814
1.28
861
1.47
907
1.65
952
1.83
995
2.00
1037
2.17
1079
2.34
1119
2.52
3400
728
1.02
779
1.23
829
1.43
877
1.61
923
1.79
967
1.97
1010
2.14
1053
2.31
1094
2.48
1135
2.66
3600
745
1.18
796
1.39
846
1.59
893
1.77
939
1.95
984
2.13
1027
2.30
1069
2.47
1111
2.64
1152
2.82
3800
763
1.36
815
1.57
864
1.76
912
1.95
958
2.13
1002
2.31
1046
2.48
1088
2.65
1129
2.82
1170
3.00
4000
783
1.55
835
1.76
884
1.96
932
2.15
978
2.33
1022
2.50
1066
2.67
1108
2.84
1149
3.02
1190
3.19
4200
805
1.77
856
1.98
906
2.17
953
2.36
999
2.54
1044
2.72
1087
2.89
1129
3.06
1171
3.23
1211
3.41
4400
828
2.00
879
2.21
929
2.41
976
2.59
1022
2.77
1067
2.95
1110
3.12
1152
3.29
1194
3.46
1235
3.64
4600
852
2.25
904
2.46
953
2.66
1001
2.85
1047
3.03
1092
3.20
1135
3.37
1177
3.54
1219
3.72
1259
3.89
4800
879
2.52
930
2.73
980
2.93
1027
3.12
1073
3.30
1118
3.47
1161
3.65
1203
3.82
1245
3.99
1285
4.16
5000
906
2.81
958
3.02
1007
3.22
1055
3.41
1101
3.59
1146
3.76
1189
3.94
1231
4.11
1273
4.28
1313
4.45
5200
936
3.12
987
3.33
1037
3.53
1084
3.72
1130
3.90
1175
4.07
1218
4.24
1260
4.42
1302
4.59
1343
4.76
5400
966
3.45
1018
3.66
1067
3.86
1115
4.05
1161
4.23
1206
4.40
1249
4.57
1291
4.74
1333
4.91
1373
5.09
5600
999
3.80
1050
4.01
1100
4.20
1147
4.39
1193
4.57
1238
4.75
1281
4.92
1323
5.09
1365
5.26
1405
5.44
5800
1032
4.16
1084
4.37
1133
4.57
1181
4.75
1227
4.93
1271
5.11
1315
5.28
1357
5.45
1398
5.62
-
-
6000
1067
4.54
1119
4.75
1168
4.95
1216
5.13
1262
5.31
1306
5.49
1350
5.66
-
-
-
-
-
-
6200
1103
4.94
1155
5.15
1204
5.34
1252
5.53
1298
5.71
-
-
-
-
-
-
-
-
-
-
Hi Static 5 HP & Drive
5 HP & Field Supplied Drive