524581-YIM-I-0512
8
Johnson Controls Unitary Products
Units may be moved or lifted with a forklift. Slotted openings in
the base rails are provided for this purpose.
LENGTH OF FORKS MUST BE A MINIMUM OF 60 INCHES.
Figure 5: Unit 4 Point Load Weight
Figure 6: Unit 6 Point Load Weight
Figure 7: Center of Gravity
Before lifting, make sure the unit weight is distributed
equally on the rigging cables so it will lift evenly.
All panels must be secured in place when the unit is
lifted.
The condenser coils should be protected from rigging
cable damage with plywood or other suitable material.
D
A
C
B
LEFT
FRONT
D
A
C
B
E
F
LEFT
FRONT
X
Y
LEFT
FRONT
Table 2:
Weights and Dimensions
Size
(Tons)
Model
Weight (lbs.)
Center of Gravity
4 Point Load Location (lbs.)
6 Point Load Location (lbs.)
Shipping Operating
X
Y
A
B
C
D
A
B
C
D
E
F
078
(6.5)
ZJ
1035
1030
39
25
245
191
260
333
170
144
122
167
195
232
090
(7.5)
ZJ
1055
1050
39
25
250
195
265
340
174
146
125
170
199
236
102
(8.5)
ZJ
1065
1060
38
24
247
184
268
360
173
141
117
171
206
253
120
(10)
ZJ
1075
1070
39
24
245
191
278
357
170
143
122
178
209
248
150
(12.5)
ZJ
1285
1280
48
24
240
281
410
350
156
173
192
280
252
227