SECTION 2 - PRE-STARTUP AND SYSTEM OPERATING PROCEDURES
FORM 160.67-O2
ISSUE DATE: 10/9/2020
2
TIMING DIAGRAM – (MANUAL START)
FIGURE
7
-
OPERA
TION
SEQUENCE
TIMING
DIAGRAM
(MANUAL
ST
AR
T)
NOTES:
1.
Text in quotations indicates a Display Message.
2.
Start-Up
Time, Run
Time, Soft Shutdown
Time, and System Coastdown
Time will vary depending on the system conditions and programmable set
-
points.
3.
Speeds and times shown, if programmable, are shown with default values.
4.
During the Run
Time, the Operating Speed may be anywhere from 3200-4500 RPM depending on Load and System Operating Conditions.
5.
Only applicable to the following shutdowns: Low W
ater
Temperature, Remote/Local Cycling (TB4-13), Remote Stop (TB4-8), Remote Stop (ISN Se
-
rial Port). Operator initiated Soft Shutdown.
"CHILLER UNLOADING BEFORE SHUTDOWN"
TURBINE
AUXILIA
RY
OIL
PUMP
ON
ENERGIZE
TURBINE STEAM RING
DRAIN SOLENOID
ENERGIZE OIL
RETURN & LIQUID
LINE SOLENOIDS
ENERGIZE
TURBINE
TRIP
& V
ACUUM
BREAKER SOLENOIDS
TURBINE
AUX. OIL
PUMP
ON
AUT
O ZEROING DIFFERENTIAL
OIL
PRESSURE
TRANSDUCERS
CHILLED LIQUID FLOW SWITCH BYP
ASS
RUN TIME (SEE
NOTE 4)
ST
AR
T-
UP
TIM
E
SLOW ROLL WA
RM-U
P
SOFT
SHUTDOWN
TIM
E
(SEE NOTE 5)
“SYSTEM COASTDOWN”
OIL
PRESSURE CHECK
COMPRESSOR OIL
PUMP
ON
HOTWELL
PUMP
ON
“COMPRESSOR SHUTDOWN TURBINE
COOLDOWN”
CONDENSER LIQUID
PUMP
ON
“ST
AR
T
SEQUENCE
INITIA
TED”
“SYSTEM ST
AR
TING”
“SLOW ROLLING” 500
1500
1000
3000
3200
4000
4500
“RAMPING
TO
RA
TED SPEED”
TIME IN SECONDS
(MINUTES)
SPEED IN RPM
CONDENSER LIQUID FLOW SWITCH BYP
ASS
VA
CUUM PUMP
ON
1800 (30.0)
360 (6.0)
70 (1.2)
35
(0.58)
50
(0.83)
45
(0.75)
13
(0.22)
10
(0.17)
0
ST
AR
T
INITIA
TED
0
“READY TO RUN”
OPERA
TO
R
PRESSES RUN AT
R
AT
ED KEY
“BEGIN SLOW ROLL”
OPERA
TO
R
PRESSES BEGIN SLOW ROLL
KEY
SHUTDOW
N0
ST
OPPED
CHILLED LIQUID
PUM
P
ON
ENERGIZE OIL
COOLER
LIQUID V
AL
VE
ACTU
AT
OR
S
“TURBINE
ST
ABILIZING”
“SYSTEM RUN”
MAN. OIL PUM
P
DISABLED
ENERGIZE
TURBINE
TRIP
SOLENOID
LD12576