SECTION 2 - PRE-STARTUP AND SYSTEM OPERATING PROCEDURES
Start Sequence is described. If there is a variation for
“Automatic Start”, it is described in the same step, fol-
lowing the Manual Start description with title of “Au-
tomatic Start.”
YST chillers are factory configured with the Speed
Control Mode set for Variable to automatically utilize
the full range of the speed, compressor PRV and hot
gas valve capabilities to control the capacity of the
chiller and provide anti-surge and override control
functions to prevent unsafe operation. The chiller may
also be configured for Fixed speed as described under
Capacity Controls later in this section. In the following
paragraphs, variable speed control is described.
To simplify the start up procedure and
provide enhanced speed control during
slow roll and low load operation, chillers
manufactured after December 2006 are
supplied with enhanced governor con-
trols. The original turbine governor valve
and actuator were replaced with a ball
valve which is field installed in the main
steam inlet line upstream of the turbine
trip valve. The valve includes a Digital
Valve Controller which utilizes the 4-20
mA governor output signal from the Op-
tiView™ panel to regulate the steam flow
to the turbine inlet and maintain accurate
speed control. For standard chillers, the
manually operated slow roll bypass valve
is no longer required to be installed by
the customer to provide stable slow roll
operation. For chillers supplied with the
Automatic Start option, the automatically
operated main steam inlet and slow roll
bypass valves are no longer supplied.