friCK i/o board analog inpuT
engliSh range
MeTriC range
loW
high
uniTS
loW
high
uniTS
Turbine Shaft End Horizontal Vibration (Optional)
0.0
5.0
Mils
0.0
127.0
Micrometers
Turbine Shaft End Vertical Vibration (Optional)
0.0
5.0
Mils
0.0
127.0
Micrometers
Turbine Supply Oil Temperature.
32.0
302.0
ºF
0.0
150.0
ºC
Turbine Shaft End Brg Temperature (Optional)
32.0
302.0
ºF
32.0
150.0
ºC
Turbine Governor End Horizontal Vibration
(Optional)
0.0
5.0
Mils
0.0
127.0
Micrometers
Turbine Governor End Vertical Vibration (Optional)
0.0
5.0
Mils
0.0
127.0
Micrometers
Turbine Gov. End Brg Temperature (Optional)
32.0
302.0
ºF
32.0
150.0
ºC
Turbine Inlet Steam Temperature
32.0
842.0
ºF
32.0
450.0
ºC
Compressor Horizontal Vibration (Optional)
0.0
2.0
In/Sec
0.0
50.8
MM/Sec
Turbine Supply Oil Pressure
0.0
30.0
PSIG
0.0
206.8
kPaG
Turbine Inlet Steam Pressure
0.0
300.0
PSIG
0.0
2068.5
kPaG
Compressor Vertical Vibration (Optional)
0.0
2.0
In/Sec
0.0
50.8
MM/Sec
Chilled Water Flow (Optional)
0.0
#6000
GPM
0.0
#378.5
L/Sec
PRV Position Feedback Potentiometer
0.0
100.0
%
0.0
100.0
%
Condenser Water Flow (Optional)
0.0
#8000
GPM
0.0
#504.7
L/Sec
Steam Flow (Optional)
0.0
#22000
LB/HR
0.0
#9979.2
Kg/Hr
Turbine First Stage Steam Pressure
0.0
**100.0
PSIG
0.0
**689.5
kPaG
Turbine Exhaust Steam Pressure
0.0
45.0
PSIA
0.0
310.3
kPaA
Turbine Speed Sensor #1
0.0
5000.0
RPM
0.0
5000.0
RPM
Turbine Speed Sensor #2
0.0
5000.0
RPM
0.0
5000.0
RPM
Hotwell Condensate Level
0.0
100.0
%
0.0
100.0
%
Surface Condenser Outlet Temperature
30
150.0
ºF
-1.11
65.6
ºC
#Value shown is example only. Full scale range is programmable on Configuration Screen 2.