![York YST Operation Manual Download Page 153](http://html2.mh-extra.com/html/york/yst/yst_operation-manual_4772857153.webp)
JOHNSON CONTROLS
153
SECTION 3 - PRINTERS
FORM 160.67-O1
ISSUE DATE: 4/1/2015
3
printer Setup
Access Level Required:
OPERATOR
Using the COMMS Screen, the Control Center must be
configured to transmit data in the same format as the
Printer is configured to receive the data. The following
values must be entered.
•
Baud Rate - Set as desired. Value selected must be
the same as Printer configuration above.
•
Data Bits - 8
•
Parity - None
•
Stop Bits - 1
printer Type
Access Level Required:
OPERATOR
Using the PRINTER Screen, the actual Printer type
connected to the Control Center must be entered. Se-
lection determines the control codes that are sent to the
Printer. These codes determine such things as lines per
inch, character width and general formatting. Available
selections are: Okidata, Weigh-Tronix and Seiko.
automatic data logging
Access Level Required:
OPERATOR
If automatic data logging is desired, a Status Report
can be automatically printed at a specified interval
beginning at a specified time, using the PRINTER
Screen. The interval is programmable over the range of
1 minute to 1440 minutes in 1 minute increments. The
first print will occur at the programmed START time
and occur at the programmed OUTPUT INTERVAL
thereafter. The time remaining until the next print is
displayed on the PRINTER Screen.
•
Automatic Printer Logging - Enables and disables
automatic data logging
• Log Start Time ‑ Enter the time the first print is
desired.
•
Output Interval - Enter the desired interval be-
tween prints.
Summary of Contents for YST