SECTION 3 - PRINTERS
FORM 160.67-O1
ISSUE DATE: 4/1/2015
3
figure 58 -
SAMPLE PRINTOUT (HISTORY)
YORK hiStORY 1
ChilleR id 0
(c) 1997 - 2004 YORK INTERNATIONAL CORPORATION
Tue 20 Apr 2004 3:20:19 PM
SYSTEM RUN
LOCAL STOP
Controls C.E09.12.00.000.00.551
Run Time 0 Days 0 Hr 33 Min
Operating Hours = 65 Hr
Number Of Starts = 5
Control Source = Local
Evaporator
-------------------------------------------------------
Leaving Chilled Active Setpoint = 42.1 ~F
Chilled Liquid Pump Start Contact = Closed
Chilled Liquid Flow Switch = Closed
Leaving Chilled Liquid Temperature = 42.0 ~F
Return Chilled Liquid Temperature = 58.0 ~F
Evaporator Pressure = 34.5 Psig
Evaporator Saturation Temperature = 39.4 ~F
Evaporator Refrigerant Temperature = 40.0 ~F
Small Temperature Difference = 2.0 ~F
Condenser
------------------------------------------------------
Condenser Liquid Pump Start Contact = Closed
Condenser Liquid Flow Switch = Closed
Leaving Condenser Liquid Temperature = 94.3 ~F
Return Condenser Liquid Temperature = 85.0 ~F
Condenser Pressure = 116.3 Psig
Condenser Saturation Temperature = 96.2 ~F
Small Temperature Difference = 1.9 ~F
Drop Leg Refrigerant Temperature = 90.0 ~F
Sub Cooling Temperature = 6.2 ~F
Compressor
-------------------------------------------------------
Discharge Temperature = 120.0 ~F
Oil Sump
-------------------------------------------------------
Oil Pump Run Output = On
Sump Oil Pressure (LOP) = 33.1 Psig
Pump Oil Pressure (HOP) = 89.4 Psig
Oil Pressure = 56.5 Psid
Oil Sump Temperature = 136.5 ~F
Oil Heater Output = On
Oil Return Solenoid = On
Variable Speed Oil Pump
-------------------------------------------------------
Oil Pump Drive Command Frequency
=
25.0 Hz
Variable Speed Oil Pump Control Mode
=
Auto
Proximity Probe
-------------------------------------------------------
High Speed Thrust Bearing Proximity Different = 2 Mils
Subcooler Level
-------------------------------------------------------
Subcooler Level Setpoint = 50 %
Subcooler Level Pulldown Time Remaining = 0 Sec
Subcooler Level = 50 %
Control Output Signal = 100 %
Subcooler Level Auto/Manual Mode
=
Auto
Hot Gas Bypass
--------------------------------------------------------
Hot Gas Ratio Calculation = 100 %
Temp Setpoint = 41.0 ~F
Hot Gas Temp Calculation = 0 %
HGV Ramp = 90 %
Control Output Signal = 100 %
HGV Auto/Manual Mode = Auto
Pre-Rotation Vanes
-------------------------------------------------------
PRV Position = 0 %
PRV Ramp = 7 %
PRV Command = 7 %
PRV Motor Switch = Open
PRV Auto/Manual Mode = Auto
Speed Control
--------------------------------------------------------
Speed Setpoint = 0 RPM
MSSP7 - Speed Control Mode = Variable Speed
Turbine Speed = 4276 RPM
Control Output Signal = 100.0 %
Turbine Rotation = Open
Speed Setpoint Auto/Manual Mode = Auto
Steam Control
-------------------------------------------------------
Inlet Temperature = 358.0 ~F
Inlet Pressure > 358.0 Psig
First Stage Pressure = 41.0 Psig
Exhaust Pressure = 1.6 Psia
Inlet Solenoid = ~F
Inlet Valve = 100 %
Bypass Solenoid = Off
Inlet Limit Switch = Closed
Slow Roll Valve = 0 %
Governor End Bearing Temperature = 170.1 ~F
Shaft End Bearing Temperature = 150.2 ~F
Turbine Vibration Sensor
--------------------------------------------------------
Governor End Horizontal Vibration = 0.5 Mils
Governor End Vertical Vibration = 0.5 Mils
Shaft End Horizontal Vibration = 0.5 Mils
Shaft End Vertical Vibration = 0.5 Mils
Turbine Solenoids
-------------------------------------------------------
Turbine Rotation = Open
Trip Solenoid = On
Trip Valve Limit Switch = Closed
Vacuum Solenoid = On
Inlet Limit Switch = Closed