Parameters relating to fans
Parameters relating to fans
Parameters
Description
Level
VS
Unit
Max.
Min.
Value
F01
Fan outlet:
0= Absent (function not available)
1= Present
F
10 (R/W)
1
0
1
F02
Operating mode:
0= Always ON
1= In parallel with the compressor (function
not available)
2= ON/OFF operation (function not availa‐
ble)
3= In parallel with the compressor and
speed regulation
U
48 (R/W)
3
0
1
F03
Minimum Triac voltage
F
49 (R/W)
step
F04
0
0
F04
Maximum Triac voltage
F
50 (R/W)
step
100
F03
100
F11
Fan start-up time
F
51 (R/W)
Seconds
120
0
0
F12
Triac impulse duration
F
52 (R/W)
Seconds
10
0
0
F13
Fan management in defrost mode
0= Fan disabled
1= Fan enabled in cool cycle mode (func‐
tion not available)
2= Fan disabled until defrost end tempera‐
ture is reached and with start-up at maxi‐
mum speed during d16
F
53 (R/W)
2
0
0
1
User manual
1.5
Operating instructions
34