Controller configuration parameters
Controller configuration parameters
Display
Description
Level
VS
Unit
Max.
Min.
Value
r01
Cool cycle set point temperature
U
41 (R/W)
°C
r14
r13
12
r02
Cool set point temperature differential
U
42 (R/W)
°C
50
0,3
2
r03
Heat cycle set point temperature
U
43 (R/W)
°C
r16
r15
40
r04
Heat cycle set point temperature differential
U
44 (R/W)
°C
50
0,3
3
r05
Compressor rotation
0= Disabled
1= FIFO type
2= Per operating hours
F
78 (R/W)
2
0
2
r06
Type of regulation
0= Proportional. Inlet temperature.
1= Proponeutral zone. Inlet temp.
2= Proportional. Outlet temperature
3= Proponeutral zone. Outlet temp.
4= By time+dead zone. Outlet temperature (coolers
only)
F
79 (R/W)
4
0
0
r07
Neutral zone differential
F
45 (R/W)
°C
50
0
1
r08
(If r06=4 only) Maximum activation time. Outlet tem‐
perature.
F
80 (R/W)
Seconds
999
r09
120
r09
(If r06=4 only) Minimum activation time. Outlet temper‐
ature.
F
81 (R/W)
Seconds
999
c04
100
r10
(If r06=4 only) Maximum deactivation time. Outlet tem‐
perature.
F
82 (R/W)
Seconds
999
r11
120
r11
(If r06=4 only) Minimum deactivation time. Outlet tem‐
perature.
F
83 (R/W)
Seconds
999
c05
100
r12
(If r06=4 only) Compressor deactivation differential.
F
46 (R/W)
°C
50
0
1
r13
Cool cycle minimum set point temperature
U
47 (R/W)
°C
r14
-40
6
r14
Cool cycle maximum set point temperature
U
48 (R/W)
°C
80
r13
20
r15
Heat cycle minimum set point temperature
U
49 (R/W)
°C
r16
-40
25
r16
Heat cycle maximum set point temperature
U
50 (R/W)
°C
80
r15
45
A
Temperature
E
COOL set point (r01)
B
First compressor
F
COOL set point (r01) +
Differential (r02)
C
HEAT set point (r03)
G
Differential /2 (r02 / 2)
D
HEAT set point (r03) +
Differential (r04)
H
Second compressor
G
A
A
A
A
B
B
H
H
C
D
E
F
User manual
1
Operating instructions
1.5
39