background image

JOHNSON CONTROLS

19

SECTION 3 - SYSTEM COMPONENTS DESCRIPTION

FORM 160.76-O1 

ISSUE DATE: 6/15/2015

3

OIL HEATER

During long idle periods, the oil in the compressor oil 

reservoir tends to absorb as much refrigerant as it can 

hold, depending upon the temperature of the oil and 

the pressure in the reservoir. As the oil temperature is 

lowered, the amount of refrigerant absorbed will be 

increased. If the quantity of refrigerant in the oil be-

comes excessive, violent oil foaming will result as the 

pressure within the system is lowered on starting. This 

foaming is caused by refrigerant boiling out of the oil 

as the pressure is lowered. If this foam reaches the oil 

pump suction, the bearing oil pressure will fluctuate 

with possible temporary loss of lubrication, causing the 

oil pressure safety cutout to actuate and stop the sys-

tem. Refer to 

Optiview™ Control Center – Operation 

and Maintenance (Form 160.54-O1)

.

MOTOR DRIVELINE

The compressor motor is an open-drip-proof, squir-

rel cage, induction type constructed to YORK design 

specifications. 60 hertz motors operate at 3570 rpm. 50 

hertz motors operate at 2975 rpm.
The open motor is provided with a D-flange, cast iron 

adapter mounted to the compressor and supported by a 

motor support.
Motor drive shaft is directly connected to the compres-

sor shaft with a flexible disc coupling. This coupling 

has all metal construction with no wearing parts to as-

sure long life, and no lubrication requirements to pro-

vide low maintenance.
For units utilizing remote Electro-Mechanical starters, 

a terminal box is provided for field connected conduit. 

Motor terminals are brought through the motor cas-

ing into the terminal box. Jumpers are furnished for 

three-lead type of starting. Motor terminal lugs are not 

furnished. Overload/over current transformers are fur-

nished with all units. 

HEAT EXCHANGERS

Evaporator and condenser shells are fabricated from 

rolled carbon steel plates with fusion welded seams. 
Heat exchanger tubes are internally enhanced type.
The evaporator is a shell and tube type with customer 

process fluid flowing inside the tubes and refrigerant 

removing heat on the shell side via evaporation. Evap-

orator codes 2*, 4*, 6* utilize a hybrid falling film de-

sign. It contains a balance of falling film technology 

to optimize efficiency, minimize refrigerant charge, 

and maintain reliable control. A specifically designed 

spray distributor provides uniform distribution of re-

frigerant over the entire length to yield optimum heat 

transfer. The hybrid falling film evaporator design has 

suction baffles around the sides and above the falling 

film section to prevent liquid refrigerant carryover into 

the compressor. 
A 1-1/2" (38 mm) liquid level sight glass is conve-

niently located on the side of the shell to aid in deter-

mining proper refrigerant charge. The evaporator shell 

contains a dual refrigerant relief valve arrangement set 

at 235 psig (16.2 barg) on Q compressor models; or 

single-relief valve arrangement, if the chiller is sup-

plied with optional refrigerant isolation valves. A 1" 

(25.4 mm) refrigerant charging valve is provided. The 

condenser is a shell and tube type, with a discharge 

gas baffle to prevent direct high velocity impingement 

on the tubes. The baffle is also used to distribute the 

refrigerant gas flow properly for most efficient heat 

transfer. An integral sub-cooler is located at the bottom 

of the condenser shell providing highly effective liquid 

refrigerant subcooling to provide the highest cycle ef-

ficiency. The condenser contains dual refrigerant relief 

valves set at 235 psig (16.2 barg).
The removable waterboxes are fabricated of steel. The 

design working pressure is 150 psig (10.3 barg) and 

the boxes are tested at 225 psig (15.5 barg). Integral 

steel water baffles are located and welded within the 

waterbox to provide the required pass arrangements. 

Stub-out water nozzle connections with ANSI/AWWA 

C-606 grooves are welded to the waterboxes. These 

nozzle connections are suitable for ANSI/AWWA 

C-606 couplings, welding or flanges, and are capped 

for shipment. Plugged 3/4" (19 mm) drain and vent 

connections are provided in each waterbox.

REFRIGERANT FLOW CONTROL

Refrigerant flow to the evaporator is controlled by a 

variable orifice.
A level sensor senses the refrigerant level in the con-

denser and outputs an analog voltage to the Microboard 

that represents this level (0% = empty; 100% = full). 

Under program control, the Microboard modulates a 

variable orifice to control the condenser refrigerant 

level to a programmed setpoint. Other setpoints affect 

the control sensitivity and response. These setpoints 

must be entered at chiller commissioning by a qualified 

service technician. Only a qualified service technician 

may modify these settings. 

Summary of Contents for YK Series

Page 1: ...WITH OPTIVIEWTM CONTROL CENTER FOR ELECTRO MECHANICAL STARTER SOLID STATE STARTER AND VARIABLE SPEED DRIVE CENTRIFUGAL LIQUID CHILLERS OPERATIONS AND MAINTENANCE New Release Form 160 76 O1 615 LD15222...

Page 2: ...his document and any referenced materials This in dividual shall also be familiar with and comply with all applicable industry and governmental standards and regulations pertaining to the task in ques...

Page 3: ...Chillers Style H Q3 Q7 with Low Voltage VSD 160 75 PW7 Renewal Parts Unit 160 76 RP1 Renewal Parts OptiView Control Center 160 54 RP1 CHANGEABILITY OF THIS DOCUMENT In complying with Johnson Controls...

Page 4: ...6 15 2015 NOMENCLATURE YK 6A 6Q Q7 EM H MOTOR CODE POWER SUPPLY for 60 Hz 5 for 50 Hz COMPRESSOR CODE CONDENSER CODE EVAPORATOR CODE MODEL STYLE Design Level Refer to YK Engineering Guide for Form 16...

Page 5: ...13 Stopping The System 13 Prolonged Shutdown 13 SECTION 3 SYSTEM COMPONENTS DESCRIPTION 15 General 15 Compressor 15 Capacity Control 15 Compressor Lubrication System 15 Oil Pump 15 Oil Heater 19 Moto...

Page 6: ...10 Oil Return System 21 FIGURE 11 Charging Oil Reservoir With Oil 22 FIGURE 12 Evacuation Of Chiller 25 FIGURE 13 Saturation Curve 27 FIGURE 14 Diagram Megging Motor Windings 28 FIGURE 15 Motor Start...

Page 7: ...in effect provides the performance of many different compressors to match various load conditions from full load with vanes wide open to minimum load with vanes completely closed SECTION 1 DESCRIPTIO...

Page 8: ...owers ext jci com 717 771 7535 YK Mod G Refrigerant Flow Thru Cross Section Diagram Falling Film Evaporator LEGEND High Pressure Vapor High Pressure Liquid Refrigerant Low Pressure Liquid Refrigerant...

Page 9: ...turn to the RUN position If the unit was previously started press the STOP RESET side of the COMPRESSOR switch and then press the START side of the switch to start the chill er When the start switch i...

Page 10: ...hutdowns Refer to Display Messages in manual Optiview Control Center Operation and Maintenance Form 160 54 O1 Figure 5 CHILLER STARTING SEQUENCE AND SHUTDOWN SEQUENCE VARIABLE SPEED DRIVE 0 10 13 45 5...

Page 11: ...he YORK chiller is designed to use less power by tak ing advantage of lower than design temperatures that are naturally produced by cooling towers throughout the operating year Exact control of conden...

Page 12: ...ndenser saturation temperature based upon condenser pressure sensed by the condenser transducer on the SYSTEM Screen 6 Check the compressor discharge temperature on the SYSTEM Screen During normal ope...

Page 13: ...he OptiView panel or rapid stop with the COM PRESSOR STOP RESET switch The compressor will stop automatically The oil pump will contin ue to run for coastdown period The oil pump will then stop automa...

Page 14: ...JOHNSON CONTROLS 14 FORM 160 76 O1 ISSUE DATE 6 15 2015 SECTION 2 SYSTEM OPERATING PROCEDURES THIS PAGE INTENTIONALLY LEFT BLANK...

Page 15: ...supplied with forced lubrication as follows 1 Compressor Drive Shaft Low Speed a Shaft seal b Front and rear journal bearings one on each side of driving gear c Low speed thrust bearing forward and r...

Page 16: ...6 15 2015 SECTION 3 SYSTEM COMPONENTS DESCRIPTION FRONT VIEW Figure 7 SYSTEM COMPONENTS FRONT VIEW VARIABLE SPEED DRIVE EVAPORATOR COMPRESSOR SUCTION RELIEF VALVES SIGHT GLASS VARIABLE SPEED OIL PUMP...

Page 17: ...7 SECTION 3 SYSTEM COMPONENTS DESCRIPTION FORM 160 76 O1 ISSUE DATE 6 15 2015 3 3 LD15223 Figure 8 SYSTEM COMPONENTS REAR VIEW DISCHARGE LINE COMPRESSOR OIL PUMP HOUSING LIQUID LINE REAR VIEW MOTOR OI...

Page 18: ...HT GLASSES OIL COOLER OIL TEMP CONTROL REFRIG THRUST COLLAR BEARING PRV INLET VALVES BEARING PINION GEAR SHAFT IMPELLER H S SHAFT SEAL LOW SPEED THRUST COVER LOW SPEED GEAR LOW SPEED GEAR REAR BEARING...

Page 19: ...ogy to optimize efficiency minimize refrigerant charge and maintain reliable control A specifically designed spray distributor provides uniform distribution of re frigerant over the entire length to y...

Page 20: ...Hot gas bypass is optional and is used to eliminate compressor surge during light load or high head op eration The OptiView control panel will automati cally modulate the hot gas valve open and closed...

Page 21: ...m the evaporator through the dehy drator to the compressor sump CHANGING THE DEHYDRATOR To change the dehydrator use the following procedure 1 Isolate the dehydrator at the stop valves 2 Remove the de...

Page 22: ...harge connection to the oil charg ing valve A located on the remote oil reservoir cover plate Refer to Figure 11 on Page 22 Do not tighten the connection at the charging valve until after the air is f...

Page 23: ...ice problem Remove obstruction Temperature difference between leaving chilled water and refrigerant in the evaporator greater than normal with normal discharge temperature Evaporator tubes dirty or re...

Page 24: ...blocked oil supply inlet Check oil inlet for blockage 8 SYMPTOM OIL PRESSURE GRADUALLY DECREASES Noted by Observation of Daily Log Sheets When oil pump VSD frequency increases to 55 hz to maintain ta...

Page 25: ...to be found by the soap test To test with R 134a proceed as follows 1 With no pressure in the system charge R 134a gas into the system through the charging valve to a pressure of 2 PSIG 14 kPa 2 Build...

Page 26: ...es and shell are heated evenly 5 Close the system charging valve and the stop valve between the vacuum indicator and the vac uum pump Then disconnect the vacuum pump leaving the vacuum indicator in pl...

Page 27: ...rior to evacuation then the saturation tempera ture recordings should follow a curve similar to the typ ical saturation curve shown as Figure 13 on Page 27 The temperature of the water in the test tub...

Page 28: ...nt charge should always be checked and trimmed when the system is shut down The refrigerant charge level must be checked after the pressure and temperature have equalized between the condenser and eva...

Page 29: ...e motor should not be run The motor should be heated to 250 F in an effort to remove moisture and obtain an acceptable reading at room ambient This can be done either by baking in a forced hot air ove...

Page 30: ...ribute to erratic performance Condenser In a condenser trouble due to fouled tubes is usually indicated by a steady rise in head pressure over a pe riod of time accompanied by a steady rise in condens...

Page 31: ...ection in the following manner if the location is not definite all the tubes will require investigations 2 Wash off both tube heads and the ends of all tubes with water Do not use carbon tetrachloride...

Page 32: ...it is shutting down on HOT High Oil Temperature or Low Oil Pressure OP change the oil filter element Examine the oil filter element for the presence of aluminum particles Aluminum gas seal rings can c...

Page 33: ...common motors MOTOR RE LUBRICATION INSTRUCTION All motor manufacturers have slightly different re quirements for the exact amount of grease to be added and the exact interval for re greasing The sugge...

Page 34: ...o see old grease coming out from the relief port Operating Temperature Normal operating temperature for grease lubricated bearings on York chillers is 40 65 degrees centigrade or 100 150 degrees Fahre...

Page 35: ...evalu ated similiar to evaporator tubes when the heating circuit is a treated closed loop Fouling could be detected as ability to meet heat load requirements decreases OIL RETURN SYSTEM 1 Change the...

Page 36: ...f applicable X 2 Perform oil analysis on compressor lube oil 1 X Perform refrigeration analysis 1 X Perform vibration analysis X Clean tubes X 2 Perform Eddy current testing and inspect tubes 2 5 Year...

Page 37: ...Fahrenheit to Celsius multiply by 5 9 or 0 5556 Example 10 0 F range x 0 5556 5 6 C range Table 3 SI METRIC CONVERSION MEASUREMENT MULTIPLY ENGLISH UNIT BY FACTOR TO OBTAIN METRIC UNIT Capacity Tons...

Page 38: ...Freedom Pennsylvania USA 17349 800 861 1001 Subject to change without notice Printed in USA Copyright by Johnson Controls 2015 www johnsoncontrols com ALL RIGHTS RESERVED Form 160 76 O1 615 Issue Dat...

Reviews: