SECTION 6 - MAINTENANCE

FORM 160.76-O1 

ISSUE DATE: 6/15/2015

6

Be sure the vacuum indicator is valved off 

while holding the system vacuum and be 

sure to open the valve between the vacuum 

indicator and the system when checking 

the vacuum after the 8 hour period.

VACUUM DEHYDRATION

To obtain a sufficiently dry system, the following in-

structions have been assembled to provide an effective 

method for evacuating and dehydrating a system in the 

field. Although there are several methods of dehydrating 

a system, we are recommending the following, as it pro-

duces one of the best results, and affords a means of ob-

taining accurate readings as to the extent of dehydration.
The equipment required to follow this method of dehy-

dration consists of a wet bulb indicator or vacuum gauge, 

a chart showing the relation between dew point tempera-

ture and pressure in inches of mercury (vacuum), (Refer 

to 

Table 2 on Page 26

) and a vacuum pump capable of 

pumping a suitable vacuum on the system.

OPERATION

Dehydration of a refrigerant system can be obtained 

by this method because the water present in the system 

reacts much as a refrigerant would. By pulling down 

the pressure in the system to a point where its satu-

ration temperature is considerably below that of room 

temperature, heat will flow from the room through the 

walls of the system and vaporize the water, allowing 

a large percentage of it to be removed by the vacuum 

pump. The length of time necessary for the dehydra-

tion of a system is dependent on the size or volume of 

the system, the capacity and efficiency of the vacuum 

pump, the room temperature and the quantity of water 

present in the system. By the use of the vacuum indi-

cator as suggested, the test tube will be evacuated to 

the same pressure as the system, and the distilled water 

will be maintained at the same saturation temperature 

as any free water in the system, and this temperature 

can be observed on the thermometer.
If the system has been pressure tested and found to be 

tight prior to evacuation, then the saturation tempera-

ture recordings should follow a curve similar to the typ-

ical saturation curve shown as 

Figure 13 on Page 27

.

The temperature of the water in the test tube will drop 

as the pressure decreases, until the boiling point is 

reached, at which point the temperature will level off 

and remain at this level until all of the water in the 

shell is vaporized. When this final vaporization has 

taken place the pressure and temperature will continue 

to drop until eventually a temperature of 35°F (1.6°C) 

or a pressure of 5 mm Hg. is reached.
When this point is reached, practically all of the air has 

been evacuated from the system, but there is still a small 

amount of moisture left. In order to provide a medium 

for carrying this residual moisture to the vacuum pump, 

nitrogen should be introduced into the system to bring 

it to atmospheric pressure and the indicator temperature 

will return to approximately ambient temperature. Close 

off the system again, and start the second evacuation.
The relatively small amount of moisture left will be 

carried out through the vacuum pump and the tem-

perature or pressure shown by the indicator should 

drop uniformly until it reaches a temperature of 35°F 

(1.6°C) or a pressure of 5 mm Hg.
When the vacuum indicator registers this temperature 

or pressure, it is a positive sign that the system is evac-

uated and dehydrated to the recommended limit. If this 

level cannot be reached, it is evident that there is a leak 

somewhere in the system. Any leaks must be corrected 

before the indicator can be pulled down to 35°F or 5 

mm Hg. in the primary evacuation.
During the primary pulldown, keep a careful watch on 

the wet bulb indicator temperature, and do not let it fall 

below 35°F (1.6°C). If the temperature is allowed to 

fall to 32°F (0°C), the water in the test tube will freeze, 

and the result will be a faulty temperature reading.

FIGURE 13 - 

SATURATION CURVE

LD00474

INDICA

TOR READING -°F

TIME

PRIMAR

Y EVACUA

TION

NITROGEN ADDED

SECONDAR

Y

       EV

ACUA

TION

REFRIGERANT CHARGING

To avoid the possibility of freezing liquid within the 

evaporator tubes when charging an evacuated system, 

only refrigerant vapor from the top of the drum or cyl-

Summary of Contents for YK Series

Page 1: ...WITH OPTIVIEWTM CONTROL CENTER FOR ELECTRO MECHANICAL STARTER SOLID STATE STARTER AND VARIABLE SPEED DRIVE CENTRIFUGAL LIQUID CHILLERS OPERATIONS AND MAINTENANCE New Release Form 160 76 O1 615 LD15222...

Page 2: ...his document and any referenced materials This in dividual shall also be familiar with and comply with all applicable industry and governmental standards and regulations pertaining to the task in ques...

Page 3: ...Chillers Style H Q3 Q7 with Low Voltage VSD 160 75 PW7 Renewal Parts Unit 160 76 RP1 Renewal Parts OptiView Control Center 160 54 RP1 CHANGEABILITY OF THIS DOCUMENT In complying with Johnson Controls...

Page 4: ...6 15 2015 NOMENCLATURE YK 6A 6Q Q7 EM H MOTOR CODE POWER SUPPLY for 60 Hz 5 for 50 Hz COMPRESSOR CODE CONDENSER CODE EVAPORATOR CODE MODEL STYLE Design Level Refer to YK Engineering Guide for Form 16...

Page 5: ...13 Stopping The System 13 Prolonged Shutdown 13 SECTION 3 SYSTEM COMPONENTS DESCRIPTION 15 General 15 Compressor 15 Capacity Control 15 Compressor Lubrication System 15 Oil Pump 15 Oil Heater 19 Moto...

Page 6: ...10 Oil Return System 21 FIGURE 11 Charging Oil Reservoir With Oil 22 FIGURE 12 Evacuation Of Chiller 25 FIGURE 13 Saturation Curve 27 FIGURE 14 Diagram Megging Motor Windings 28 FIGURE 15 Motor Start...

Page 7: ...in effect provides the performance of many different compressors to match various load conditions from full load with vanes wide open to minimum load with vanes completely closed SECTION 1 DESCRIPTIO...

Page 8: ...owers ext jci com 717 771 7535 YK Mod G Refrigerant Flow Thru Cross Section Diagram Falling Film Evaporator LEGEND High Pressure Vapor High Pressure Liquid Refrigerant Low Pressure Liquid Refrigerant...

Page 9: ...turn to the RUN position If the unit was previously started press the STOP RESET side of the COMPRESSOR switch and then press the START side of the switch to start the chill er When the start switch i...

Page 10: ...hutdowns Refer to Display Messages in manual Optiview Control Center Operation and Maintenance Form 160 54 O1 Figure 5 CHILLER STARTING SEQUENCE AND SHUTDOWN SEQUENCE VARIABLE SPEED DRIVE 0 10 13 45 5...

Page 11: ...he YORK chiller is designed to use less power by tak ing advantage of lower than design temperatures that are naturally produced by cooling towers throughout the operating year Exact control of conden...

Page 12: ...ndenser saturation temperature based upon condenser pressure sensed by the condenser transducer on the SYSTEM Screen 6 Check the compressor discharge temperature on the SYSTEM Screen During normal ope...

Page 13: ...he OptiView panel or rapid stop with the COM PRESSOR STOP RESET switch The compressor will stop automatically The oil pump will contin ue to run for coastdown period The oil pump will then stop automa...

Page 14: ...JOHNSON CONTROLS 14 FORM 160 76 O1 ISSUE DATE 6 15 2015 SECTION 2 SYSTEM OPERATING PROCEDURES THIS PAGE INTENTIONALLY LEFT BLANK...

Page 15: ...supplied with forced lubrication as follows 1 Compressor Drive Shaft Low Speed a Shaft seal b Front and rear journal bearings one on each side of driving gear c Low speed thrust bearing forward and r...

Page 16: ...6 15 2015 SECTION 3 SYSTEM COMPONENTS DESCRIPTION FRONT VIEW Figure 7 SYSTEM COMPONENTS FRONT VIEW VARIABLE SPEED DRIVE EVAPORATOR COMPRESSOR SUCTION RELIEF VALVES SIGHT GLASS VARIABLE SPEED OIL PUMP...

Page 17: ...7 SECTION 3 SYSTEM COMPONENTS DESCRIPTION FORM 160 76 O1 ISSUE DATE 6 15 2015 3 3 LD15223 Figure 8 SYSTEM COMPONENTS REAR VIEW DISCHARGE LINE COMPRESSOR OIL PUMP HOUSING LIQUID LINE REAR VIEW MOTOR OI...

Page 18: ...HT GLASSES OIL COOLER OIL TEMP CONTROL REFRIG THRUST COLLAR BEARING PRV INLET VALVES BEARING PINION GEAR SHAFT IMPELLER H S SHAFT SEAL LOW SPEED THRUST COVER LOW SPEED GEAR LOW SPEED GEAR REAR BEARING...

Page 19: ...ogy to optimize efficiency minimize refrigerant charge and maintain reliable control A specifically designed spray distributor provides uniform distribution of re frigerant over the entire length to y...

Page 20: ...Hot gas bypass is optional and is used to eliminate compressor surge during light load or high head op eration The OptiView control panel will automati cally modulate the hot gas valve open and closed...

Page 21: ...m the evaporator through the dehy drator to the compressor sump CHANGING THE DEHYDRATOR To change the dehydrator use the following procedure 1 Isolate the dehydrator at the stop valves 2 Remove the de...

Page 22: ...harge connection to the oil charg ing valve A located on the remote oil reservoir cover plate Refer to Figure 11 on Page 22 Do not tighten the connection at the charging valve until after the air is f...

Page 23: ...ice problem Remove obstruction Temperature difference between leaving chilled water and refrigerant in the evaporator greater than normal with normal discharge temperature Evaporator tubes dirty or re...

Page 24: ...blocked oil supply inlet Check oil inlet for blockage 8 SYMPTOM OIL PRESSURE GRADUALLY DECREASES Noted by Observation of Daily Log Sheets When oil pump VSD frequency increases to 55 hz to maintain ta...

Page 25: ...to be found by the soap test To test with R 134a proceed as follows 1 With no pressure in the system charge R 134a gas into the system through the charging valve to a pressure of 2 PSIG 14 kPa 2 Build...

Page 26: ...es and shell are heated evenly 5 Close the system charging valve and the stop valve between the vacuum indicator and the vac uum pump Then disconnect the vacuum pump leaving the vacuum indicator in pl...

Page 27: ...rior to evacuation then the saturation tempera ture recordings should follow a curve similar to the typ ical saturation curve shown as Figure 13 on Page 27 The temperature of the water in the test tub...

Page 28: ...nt charge should always be checked and trimmed when the system is shut down The refrigerant charge level must be checked after the pressure and temperature have equalized between the condenser and eva...

Page 29: ...e motor should not be run The motor should be heated to 250 F in an effort to remove moisture and obtain an acceptable reading at room ambient This can be done either by baking in a forced hot air ove...

Page 30: ...ribute to erratic performance Condenser In a condenser trouble due to fouled tubes is usually indicated by a steady rise in head pressure over a pe riod of time accompanied by a steady rise in condens...

Page 31: ...ection in the following manner if the location is not definite all the tubes will require investigations 2 Wash off both tube heads and the ends of all tubes with water Do not use carbon tetrachloride...

Page 32: ...it is shutting down on HOT High Oil Temperature or Low Oil Pressure OP change the oil filter element Examine the oil filter element for the presence of aluminum particles Aluminum gas seal rings can c...

Page 33: ...common motors MOTOR RE LUBRICATION INSTRUCTION All motor manufacturers have slightly different re quirements for the exact amount of grease to be added and the exact interval for re greasing The sugge...

Page 34: ...o see old grease coming out from the relief port Operating Temperature Normal operating temperature for grease lubricated bearings on York chillers is 40 65 degrees centigrade or 100 150 degrees Fahre...

Page 35: ...evalu ated similiar to evaporator tubes when the heating circuit is a treated closed loop Fouling could be detected as ability to meet heat load requirements decreases OIL RETURN SYSTEM 1 Change the...

Page 36: ...f applicable X 2 Perform oil analysis on compressor lube oil 1 X Perform refrigeration analysis 1 X Perform vibration analysis X Clean tubes X 2 Perform Eddy current testing and inspect tubes 2 5 Year...

Page 37: ...Fahrenheit to Celsius multiply by 5 9 or 0 5556 Example 10 0 F range x 0 5556 5 6 C range Table 3 SI METRIC CONVERSION MEASUREMENT MULTIPLY ENGLISH UNIT BY FACTOR TO OBTAIN METRIC UNIT Capacity Tons...

Page 38: ...Freedom Pennsylvania USA 17349 800 861 1001 Subject to change without notice Printed in USA Copyright by Johnson Controls 2015 www johnsoncontrols com ALL RIGHTS RESERVED Form 160 76 O1 615 Issue Dat...

Reviews: