Johnson Controls Unitary Products
47
HEATING PERFORMANCE DATA
CONDENSING UNIT MODEL NO
YHJD60S41S7
AIR TEMP.
ENTERING
OUTDOOR UNIT (°F)
AIR TEMP.
ENTERING
INDOOR
COIL
ID CFM
1600
1800
2000
MBH
COP
KW
MBH
COP
KW
MBH
COP
KW
60
60
72.1
3.76
5.02
71.1
3.77
4.85
70.1
3.79
4.68
70
70.9
3.40
5.52
70.6
3.44
5.34
70.3
3.49
5.17
80
69.8
3.09
6.02
70.2
3.16
5.84
70.5
3.23
5.66
47
60
62.7
3.68
4.39
62.4
3.69
4.28
62.1
3.71
4.16
70
61.1
3.30
4.82
61.1
3.52
4.42
61.1
3.76
4.02
80
59.6
2.98
5.26
59.9
3.35
4.56
60.1
3.82
3.87
40
60
55.6
3.52
4.04
55.9
3.55
3.95
56.2
3.58
3.86
70
54.3
3.14
4.47
54.5
3.17
4.36
54.8
3.21
4.26
80
52.9
2.82
4.90
53.1
2.85
4.78
53.3
2.89
4.66
30
60
45.3
3.16
3.60
45.7
3.19
3.53
46.1
3.21
3.46
70
43.9
2.85
3.91
44.3
2.87
3.86
44.8
2.89
3.81
80
42.4
2.58
4.22
43.0
2.59
4.19
43.5
2.60
4.15
17
60
38.0
2.83
3.33
38.5
2.85
3.30
39.1
2.86
3.26
70
35.5
2.48
3.60
36.5
2.52
3.58
37.5
2.55
3.56
80
33.0
2.16
3.87
34.4
2.23
3.86
35.9
2.28
3.86
10
60
32.3
2.55
3.11
32.8
2.57
3.07
33.3
2.60
3.02
70
31.3
2.27
3.44
31.5
2.28
3.38
31.8
2.28
3.33
80
30.3
2.04
3.76
30.2
2.03
3.70
30.2
2.02
3.64
NOTE:
ALL CAPACITIES ARE NET, WITH INDOOR FAN HEAT ALREADY DEDUCTED. KW VALUES ARE FOR THE SYSTEM (OUT-
DOOR + INDOOR).
Yellow
shaded cells are AHRI High Heating conditions.
Orange
shaded cells are AHRI Low Heating conditions.
Multipliers for determining the performance with other indoor sections.
Some of the combinations shown in these multiplier tables are not valid for use in the U.S.A. Please see the Capacity
Tables in the front of this Technical Guide for US matches, and verify matchups in the online AHRI directory at
www.ahridirectory.org
before sale. The matches shown at the end of this Technical Guide are for use in Canda Only.
Air Handlers
Coils
MBH
COP
KW
–
FC/MC62D
0.93
1.03
1.04
–
FC64D
0.93
1.03
1.04
AHE60D
–
0.93
1.07
1.00
AHV60D
–
0.93
1.03
1.04
MV20D
FC/MC62D
0.93
1.06
1.01
MV20D
FC64D
0.93
1.09
0.98
MX20DN21
FC/MC62D
0.93
1.07
1.00
MX20DN21
FC64D
0.93
1.10
0.97
Furnaces
Coils
MBH
COP
KW
T*(8,L)V*C20
FC/MC62D
0.93
1.02
1.05
T*(8,L)V*C20
FC64D
0.93
1.09
0.99
T*9V*C20
FC/MC62D
0.93
1.02
1.06
T*9V*C20
FC64D
0.93
1.05
1.02
T*9V*D20
FC/MC62D
0.93
1.02
1.05
T*9V*D20
FC64D
0.93
1.06
1.02
TM8X100C20MP11
FC/MC62D
0.93
1.03
1.04
TM8X100C20MP11
FC64D
0.93
1.06
1.02
Furnaces
Coils
MBH
COP
KW
TM8X120C20MP11
FC/MC62D
0.93
1.03
1.04
TM8X120C20MP11
FC64D
0.93
1.06
1.02
TM9E100C20MP11
FC/MC62D
0.93
1.01
1.06
TM9E100C20MP11
FC64D
0.93
1.04
1.03
TM9E120D20MP11
FC/MC62D
0.93
1.01
1.06
TM9E120D20MP11
FC64D
0.93
1.03
1.04
TMLX100C20MP11
FC/MC62D
0.93
1.03
1.04
TMLX100C20MP11
FC64D
0.93
1.06
1.02
TMLX120C20MP11
FC/MC62D
0.93
1.03
1.04
TMLX120C20MP11
FC64D
0.93
1.06
1.02
Y*(8,L)C*C20
FC/MC62D
0.93
1.02
1.05
Y*(8,L)C*C20
FC64D
0.93
1.09
0.99
Y*9C*C20
FC/MC62D
0.93
1.02
1.06
Y*9C*C20
FC64D
0.93
1.05
1.02
Y*9C*D20
FC/MC62D
0.93
1.02
1.05
Y*9C*D20
FC64D
0.93
1.06
1.02
571209-YTG-F-0615