9. Technical Data
Operational Limits
Pressure Drop
The expected waterside pressure drop at design flow is provided on the particular sales order form header. When
rated in accordance with AHRI-550, the actual pressure drop for clean tubes is permitted to be lower than or 15%
greater than the stated value.
To determine flow or waterside pressure drop at conditions other than sales order design, use the following relationship
to calculate the unknown parameter. Ensure consistent units of measure are used during calculation:
Min. Max. Min. Max. Min. Max. Min. Max.
Liquid outlet temperature (water)
°C
Flow rate
l/s
9
27
11
32
14
39
18
48
Maximum working pressure
barg
Liquid outlet temperature
°C
Flow rate
l/s
11
33
13
38
16
48
20
58
Maximum working pressure
barg
Refrigerant System High pressure side
barg
Power supply voltage
V
System water volume - Air Conditioning
l
Air temperature surrounding unit
°C
Min. Max. Min. Max. Min. Max. Min. Max.
Liquid outlet temperature (water)
°C
Flow rate
l/s
25
75
27
79
40
122
40
120
Maximum working pressure
barg
Liquid outlet temperature
°C
Flow rate
l/s
30
88
33
98
45
133
50
144
Maximum working pressure
barg
Refrigerant System High pressure side
barg
Power supply voltage
V
System water volume - Air Conditioning
l
Air temperature surrounding unit
°C
4.4 to 43.3
18
380V, 400V, 415V 3Ø, 50Hz (nominal)
700
829
1029
1111
Cooling liquid
18 to 43
10
Chilled liquid
2.2 to 21
10
YGWH Models
260
300
330
375
Chilled liquid
10
YGWH Models
Cooling liquid
4.4 to 43.3
799
225
115
18
145
18 to 43
10
180
2.2 to 21
380V, 400V, 415V 3Ø, 50Hz (nominal)
401
501
638
Design
Design pressure
Actual
Actual pressure
flow
drop
flow
=
drop
Summary of Contents for YGWH 115
Page 2: ......
Page 10: ...1 6 EN Form 6S6I B01C EOMA EN 0318 Page Left Intentionally Blank...
Page 24: ...4 8 EN Form 6S6I B01C EOMA EN 0318 Customer Connections...
Page 40: ...6 14 EN Form 6S6I B01C EOMA EN 0318 Page Left Intentionally Blank...
Page 58: ...10 2 EN Form 6S6I B01C EOMA EN 0318 Page Left Intentionally Blank...