![York YGWH 115 Installation, Commissioning & Operation Download Page 52](http://html1.mh-extra.com/html/york/ygwh-115/ygwh-115_installation-commissioning-and-operation_4194873052.webp)
8-8
EN
Form 6S6I-B01C-EOMA-EN (0318)
Sensor Calibration Charts
Chilled Leaving/Return Liquid and Cooling Leaving/Return Liquid Temperature Sensors
Discharge Temperature Sensor
Temperature °C
-5
-3
-1
1
3
5
7
9
11
13
15
Resistance k
Ω
42.82
38.53
3 4.71
31.32
28.29
2 5.59
23.17 21. 01 1 9.07 17.33 15. 77
Temperature °C
17
19
21
23
25
27
29
31
33
35
37
Resistance k
Ω
14.37
13.1
11.96
10.93
10
9.16
8.4
7.71
7 .085 6.517
6
Temperature °C
0
3
6
9
12
15
18
21
24
27
30
Resistance k
Ω
166.75 142 .9 1 22.81 105.83 91.4 43 7 9.219 68.804 59.908 52.291 45.752 40.125
Temperature °C
33
36
39
42
45
48
51
54
57
60
63
Resistance k
Ω
35.272 31.0 76 2 7.44 24.283 21.5 35 1 9.137 17.042 15.206 13.595 12.178 10.929