6-10
EN
Form 6S6I-B01C-EOMA-EN (0318)
The following parameters can be checked on the details pages:
is used to clear faults,
is used to clear saved historical fault data.
is used to create trends of the parameters above using the ID to select. Up to five trends of
different parameters can be created. This feature is useful for monitoring parameters during fault
diagnosis, and when unit performance is below standard.
ID
Parameter
UOM
ID
Parameter
UOM
962 Leaving Condenser Temp.
°C
963 Return Condenser Temp.
°C
964 Leaving Chilled Temp.
°C
965 Return Chilled Temp.
°C
1165 Evaporator Pressure
kPa
943 Condenser Pressure
kPa
1206 Discharge Temp.
°C
1207 Oil Pressure
kPa
1221 Run Current
A
1223 Percent FLA
%
949 Liquid Level
%
1121 Level Control AO
%
1403 Motor Temperature A
°C
1404 Motor Temperature B
°C
1405 Motor Temperature C
°C
1069 HMI Start/Stop
901 Chilled Liquid Flow Switch
902 Mode Switch
1375 High Pressure Switch
904 Low Oil Level Switch
1376 Motor Internal Protect/Power Protect
906 External Interlock
1377 Starter Running Feedback
908 Remote Switch
909 EM Stop
1378 Starter Fault Feedback
911 Condenser Liquid Flow Switch
927 Liquid Pump
1383 Slide Valve Load
1384 Slide Valve Unload
1391 Compressor Star Contact
1392 Compressor Delta Contact
930 Oil Heater
931 Hot Gas Bypass
932 Alarm
935 Unit Running
1393 Liquid Injection Oil Cooling
1394 Oil Supply Circuit
1074 Total Run Hour
H
1072 Number of Starts
1080 Unit Type
1082 Control Source
1084 Running Mode
1227 FLA
A
1417 Over Current Percent
%
1232 Minimum Load Percent
%
1418 Leaving Chiller Temp. Setpoint
°C
1419 Evap. Low Press. Stop Setpoint
kPa
1420 Cond. High Temp. Stop Setpoint
°C
1421 High Press. Stop Setpoint
kPa
1166 Standby Anti-Freezing
1167 Smart Freeze
1323 Frequency Command
Hz
1324 Frequency Running
Hz
1325 BUS Voltage
V
1326 Output Voltage
V
1327 Output Current
A
1328 Output Power
kW
1329 Heatsink Temperature
°C
1367 VSD Run Status
Summary of Contents for YGWH 115
Page 2: ......
Page 10: ...1 6 EN Form 6S6I B01C EOMA EN 0318 Page Left Intentionally Blank...
Page 24: ...4 8 EN Form 6S6I B01C EOMA EN 0318 Customer Connections...
Page 40: ...6 14 EN Form 6S6I B01C EOMA EN 0318 Page Left Intentionally Blank...
Page 58: ...10 2 EN Form 6S6I B01C EOMA EN 0318 Page Left Intentionally Blank...